Routing Wiring Ducts

Installation

 

 

 

 

 

 

 

 

 

 

Section 3-1

Routing Wiring Ducts

Install the wiring ducts at least 20 mm away from the FQM1 and any other

 

objects, (e.g., ceiling, wiring ducts, structural supports, and devices) to pro-

 

vide enough space for air circulation and replacement of Modules.

 

Input duct

Output duct

Power duct

 

 

 

 

 

 

 

 

200 mm min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PLC

FQM1

FQM1

FQM1

Breakers, fuses

FQM1

Power equipment such as transformers and magnetic relays

Fuses, relays, timers, etc. (NOT heat-generating equipment, power equipment, etc.)

Terminal blocks

Terminal blocks

for FQM1

for power

 

equipment