Omron FQM1-MMP21 9-2-7Memory Error Check, 9-2-8Program Error Check, Error Processing, Section

Models: FQM1-MMP21 FQM1-MMA21 FQM1-CM001

1 414
Download 414 pages 44.52 Kb
Page 275
Image 275
9-2-7 Memory Error Check

Error Processing

Section 9-2

9-2-7 Memory Error Check

Memory error occurred

Flash Memory Error Flag

ON

 

(A403.10) ON?

 

OFF

 

Was power

interrupted while backing Yes up memory with the CX-

Programmer?

No

9-2-8 Program Error Check

Program error occurred

Task Error Flag

ON

(A405.12) ON?

 

OFF

 

No END Error Flag

ON

(A405.11) ON?

 

OFF

 

The internal flash memory's rewrite limit has been exceeded. Replace the Module.

The power supply was turned OFF during a memory backup. Transfer the data again.

There was a hardware failure in the internal memory. Replace the Module.

The called task does not exist. Check the MSKS instruction that enables the interrupt task with the corresponding task number.

There isn't an END instruciton in the program. Add an END instruction.

Turn the power supply OFF and ON again.