Omron FQM1-MMP21, FQM1-CM001 Cycle Time Settings, Section, Normal Operation, Auxiliary Area Bits

Models: FQM1-MMP21 FQM1-MMA21 FQM1-CM001

1 414
Download 414 pages 44.52 Kb
Page 140
Image 140
Normal Operation

Cycle Time Settings

Section 5-6

5-6-4 Clearing Constant Cycle Time Exceeded Errors

When using the constant cycle time function, normally the cycle time will no longer stay constant (i.e., will vary depending on the real cycle time) if the constant cycle time is exceeded once. To return to a constant cycle time even if the cycle time has been exceeded once, turn ON the Constant Cycle Time Exceeded Error Clear Bit (A509.15) (i.e., set to 1).

This function allows a constant cycle time to be restored and variations in I/O processing time to be kept to a minimum even if the cycle time is temporarily long as a result of special processing, e.g., initialization at the start of user programs in each Module.

Normal Operation

The constant cycle time function is cleared if the cycle time exceeds the set constant cycle time.

Cycle time

 

Constant cycle

Constant cycle time cleared

time value

 

Constant cycle time

Real cycle time

Time

Constant Cycle Time Exceeded Error Clear Function

The constant cycle time function can be enabled again by turning ON the

Constant Cycle Time Exceeded Clear Bit.

Cycle time

Constant cycle time cleared

 

Constant cycle

Constant cycle time

time

 

 

enabled again

 

 

Constant cycle

 

 

 

time

 

 

 

Real cycle time

 

 

 

 

 

Time

Constant Cycle Time

 

 

 

Exceeded Flag

 

 

 

(A404.05)

 

 

 

Constant Cycle Time

 

 

 

Exceeded Error Clear Bit

 

ON for 1 scan

 

(A509.15)

 

 

 

 

 

Auxiliary Area Bits

 

 

 

Bit

Function

Controlled by

Constant Cycle Time A509.15

OFF to ON:

 

User

Exceeded Error

Constant cycle time exceeded

 

Clear Bit

error cleared.

 

 

117

Page 140
Image 140
Omron FQM1-MMP21 Cycle Time Settings, Section, Normal Operation, Constant Cycle Time Exceeded Error Clear Function