Omron FQM1-MMP21, FQM1-CM001 Section, Absolute Encoder, Output Data, Acquiring Method, 1,2,3

Models: FQM1-MMP21 FQM1-MMA21 FQM1-CM001

1 414
Download 414 pages 44.52 Kb
Page 230
Image 230
Absolute Encoder

Functions for Servo Drivers Compatible with Absolute Encoders

Section 7-7

7-7-10 Overview of Absolute Encoder Output Data Acquire

Behavior of the Servo Driver Compatible with an Absolute Encoder

The SEN signal being turned ON, the Servo Driver behaves in the following manner:

1,2,3...

1. The Servo Driver transmits the state of the absolute encoder when the

 

SEN signal is turned ON.

 

The operation proceeds in the following order:

 

a. Transmits the multi-turn data (how many revolutions the axis of the ro-

 

tary encoder made) with the serial communications.

 

b. Transmits the initial incremental pulse (difference between present po-

 

sition and origin) with phase differential pulse output.

 

2. After transmitting the absolute value data, transmits the pulse train corre-

 

sponding to the rotational displacement. (Transmits the same pulse as an

 

incremental encoder)

Absolute Encoder

Use the following procedure to read the absolute encoder output data from a

Output Data

Servo Driver to the Motion Control Module:

Acquiring Method

 

Step 1 (Required): Setting

Setting the Pulse Input Method

Step 2 (Required): Acquiring the Encoder Status when the SEN Signal is Turned ON

Set the pulse input method in the System Setup. Select one of the following 5 methods:

Phase differential 1, 2, or 4, increment/decrement pulse input, or pulse + direction. Set the pulse input method to a phase differential input.

Setting the Input Pulse Counting Speed

Set the input pulse counting speed to 500 kHz. To do so, set the input pulse counting speed to 500 kHz in the System Setup.

Setting the Counter Operation

Set the Counter 1 Counter operation in the System Setup. Select one of the following three counter operations for counting the encoder output.

Absolute linear (CW) counter

Absolute linear (CW+) counter

Absolute circular counter

Be sure to set the System Setup’s Counter 1 Counter operation so that it agrees with the Servo Driver’s reverse rotation mode setting.

Setting the Absolute Encoder Resolution

Set absolute encoder resolution, which is the number of pulses received from the Servo Driver for each revolution of the encoder.

Consider both the Servo Driver's encoder dividing rate setting and the Motion Control Module's pulse input multiplier setting (with the System Setup’s pulse input method setting). For example, set the resolution to FA0 (4,000) when the Servo Driver’s rate is 1,000 and the Motion Control Module’s multiplier is 4.

Turn ON the Absolute Number of Rotations Read Bit (A610.07) from the lad- der program. At this point, the SEN signal will go ON (high level). Leave the SEN signal ON during operation, just like the RUN signal.