Omron FQM1-MMP21, FQM1-CM001, FQM1-MMA21 Auxiliary Area Allocations, Appendix D, A612

Models: FQM1-MMP21 FQM1-MMA21 FQM1-CM001

1 414
Download 414 pages 44.52 Kb
Page 380
Image 380
Manual background

Auxiliary Area Allocations

Appendix D

 

 

 

 

 

Address

Bits

 

Name

Function

 

 

 

 

 

A612

00 to 15

High-

Range Comparison Execution

Contains the CTBL(882) execution results for range comparison.

 

 

speed

Results Flags

Bits 00 to 15 correspond to ranges 1 to 16.

 

 

counter 1

 

OFF: No match

 

 

monitor

 

ON: Match

 

 

data

 

 

 

 

 

A613

00 to 15

Output Bit Pattern

Contains the output bit pattern when a match is found for

 

 

 

 

 

CTBL(882) execution results for range comparison

 

 

 

 

Note If more than one match is found, an OR of the output bit

 

 

 

 

patterns with matches will be stored here.

 

 

 

 

 

A614

00 to 15

High-

Range Comparison Results

Same as for high-speed counter 1 monitor data.

 

 

speed

 

 

A615

00 to 15

Output Bit Pattern

 

counter 2

 

 

 

monitor

 

 

 

 

data

 

 

 

 

 

 

 

A620 to

00 to 15

Pulse Output 1 PV

Contains the pulse output PV as an 8-digit hexadecimal number.

A621

 

Note This item applies when the operation

Relative mode: 00000000 to FFFFFFFF hex

 

 

mode is relative pulse output, absolute pulse

Absolute linear mode: 80000000 to 7FFFFFFF hex

 

 

output in linear mode, absolute pulse output in

Absolute circular mode: 00000000 to circular maximum count

 

 

circular mode, or electronic cam mode.

 

 

 

 

 

One-shot Pulse Output 1 ON Time

Contains the time that the one-shot pulse output has been ON as

 

 

Note This item applies when the operation

an 8-digit hexadecimal number.

 

 

0000 0000 to 0000 270F (unit: set by STIM(980))

 

 

mode is one-shot output mode.

 

 

 

 

 

 

Pulse Time Measurement 1

Contains the time measured by the pulse counter as an 8-digit

 

 

Note This item applies when the operation

hexadecimal number.

 

 

0000 0000 to FFFF FFFF hex (unit: set by STIM(980))

 

 

mode is time measurement mode using a pulse

 

 

counter.

 

 

 

 

 

 

A622 to

00 to 15

Pulse Output 2 PV

Same as for Pulse Output 1 PV.

A623

 

 

 

 

 

One-shot Pulse Output 2 ON Time

Same as for One-shot Pulse Output 1 ON time.

 

 

 

 

 

 

 

 

Pulse Time Measurement 2

Same as for Pulse Time Measurement 1.

 

 

 

 

 

A624

00

Pulse

Pulse Output Completed Flag

OFF: Pulse output not completed (OFF during pulse output).

 

 

Output 1

 

ON: Pulse output completed (ON when pulse distribution has

 

 

Status

 

been completed).

 

 

 

 

 

 

01

 

Pulse Output Set Flag

OFF: Pulse output amount not set by PULS(886).

 

 

 

 

ON: Pulse output amount set by PULS(886).

 

 

 

 

 

 

02

 

Target Frequency Not Reached Flag

OFF: Target speed has been reached during pulse output for

 

 

 

 

PLS2(887).

 

 

 

 

ON: Decelerated before reaching the target speed during pulse

 

 

 

 

output for PLS2(887).

 

 

 

 

 

 

03

 

Target Comparison Flag

OFF: Comparison stopped.

 

 

 

 

ON: Comparison in progress.

 

 

 

 

 

 

04

 

Independent Pulse Output Flag

OFF: Pulses not being output or being output continuously.

 

 

 

 

ON: Pulses being output.

 

 

 

 

 

 

05

 

PLS2 Positioning Flag

OFF: Not positioning.

 

 

 

 

ON: Positioning in progress.

 

 

 

 

 

 

06

 

Accelerating/Decelerating Flag

OFF: No output or constant-speed output.

 

 

 

 

ON: Acceleration or deceleration in progress for ACC(888) or

 

 

 

 

PLS2(887).

 

 

 

 

 

 

07

 

Pulse Output Flag

OFF: Pulse output stopped.

 

 

 

 

ON: Pulse output in progress.

 

 

 

 

 

A625

00

Pulse

Pulse Output Completed Flag

Same as for Pulse Output 1 Status.

 

 

Output 2

 

 

 

01

Pulse Output Set Flag

 

 

Status

 

 

 

 

 

 

02

 

Target Frequency Not Reached Flag

 

 

 

 

 

 

 

03

 

Target Comparison Flag

 

 

 

 

 

 

 

04

 

Independent Pulse Output Flag

 

 

 

 

 

 

 

05

 

PLS2 Positioning Flag

 

 

 

 

 

 

 

06

 

Accelerating/Decelerating Flag

 

 

 

 

 

 

 

07

 

Pulse Output Flag

 

 

 

 

 

 

357