Omron FQM1-MMA21 Pulse Outputs, Section, Pulse Output Operations, Mode, Frequency changes

Models: FQM1-MMP21 FQM1-MMA21 FQM1-CM001

1 414
Download 414 pages 44.52 Kb
Page 196
Image 196
Pulse Output Operations

Pulse Outputs

Section 7-6

Pulse Output Operations

The following table shows the operations that can be performed with the pulse output function.

Mode

Frequency changes

Description

Procedure

Example

 

 

 

Instruc-

Settings

 

 

 

 

tions

 

 

Continu-

Frequency

The frequency is

SPED(88

Port,

Use when

ous mode

 

changed in

5)

CW/CCW,

changing fre-

(Speed

Target

steps (up or

Continu-

quency in

frequency

control)

down) during

 

ous,

steps. (See

 

SPED(88

 

Present

pulse output.

Target fre-

page 190.)

 

5)

 

 

quency

 

 

frequency

 

 

 

 

 

 

 

Time

 

 

 

 

 

SPED executed.

 

 

 

 

 

Frequency

The frequency is

ACC(888)

Port,

Use when

 

 

accelerated or

or

CW/CCW,

accelerating

 

Target

decelerated

SPED(88

Continu-

frequency at

 

frequency Acceleration rate

 

from the present

5)

ous,

a fixed rate.

 

 

 

Present

frequency at a

Accelera-

(See

 

frequency

fixed rate.

ACC(888)

tion/decel-

page 190.)

 

Time

 

eration

 

 

ACC executed.

 

 

rate,

 

 

 

 

Target fre-

 

 

 

 

 

 

 

 

 

 

quency

 

173

Page 196
Image 196
Omron FQM1-MMA21 Pulse Outputs, Section, Pulse Output Operations, Mode, Frequency changes, Description, Procedure, Example