Cycle Time Settings

Section 5-6

Coordinator Module

Motion

Control

Module

Constant cycle time

Waiting for I/O refresh Waiting to

to become constant

synchronize

Processing

I/O refresh

Constant I/O

 

refresh timing

 

 

Constant cycle time

Waiting for I/O refresh

Waiting to

to become constant

synchronize

Processing

I/O refresh

Constant I/O

 

 

refresh timing

 

 

Note When the constant cycle time function is enabled for the Motion Control Mod- ule in ASync Mode, the Motion Control Module's cycle time will be constant.

5-6-2 Watch Cycle Time Function

If the real cycle time is longer than the set watch cycle time, operation will stop for all Modules and the Cycle Time Too Long Flag (A401.08) in the Auxiliary Area will turn ON.

System Setup

Tab page

Name

Details

Default

 

 

 

 

Timer/Peripheral Servic-

Cycle Time

0.1 to 100.0 ms

Variable

ing or Cycle Time

 

(unit: 0.1 ms)

 

 

 

 

 

 

Watch Cycle Time

1 to 100 ms

50 ms

 

 

(unit: 1 ms)

 

 

 

 

 

!Caution If the Cycle Time Too Long Flag turns ON for one Module in Sync Mode, the Cycle Time Too Long Flag will turn ON for all Modules.

Note The settings are made using CX-Programmer Ver. 5.0@ menus.

Cycle Time Too Long Flag

Name

Address

Details

 

 

 

Cycle Time Too Long

A401.08

Turns ON if the cycle time PV exceeds the

Flag

 

Watch Cycle Time in the System Setup.

5-6-3 Cycle Time Monitoring Function

Every cycle, the maximum cycle time is stored in A206 and A207 and the PV is stored in A208 and A209 in the Auxiliary Area.

Auxiliary Area Words

Name

Addresses

Meaning

 

 

 

Maximum Cycle

A206 to A207

The maximum cycle time value is stored in

Time

 

binary each cycle. The time is measured in

 

 

0.01-ms units.

 

 

 

Cycle Time PV

A208 to A209

The cycle time PV is stored in binary each

 

 

cycle. The time is measured in 0.01-ms

 

 

units.

 

 

 

The average cycle time for the last 8 scans can also be read from the CX-Pro- grammer.

Note The FQM1 can skip program areas that do not need to be executed by using the JMP-JME instructions to shorten cycle times.