CX-ProgrammerSection 8-1

8-1

CX-Programmer

 

 

 

Connect the CX-Programmer Support Software to the Coordinator Module to

 

 

create and monitor programs for all Modules. While monitoring the ladder pro-

 

 

grams in Motion Control Modules, it is possible to input operation conditions

 

 

for monitoring the I/O of the Coordinator Module, and to debug programs.

 

 

The FQM1 Patch Software is required to create the FQM1 ladder program,

 

 

make System Setup settings, and monitor or debug operation.

 

 

The FQM1 Patch Software must be installed for the CX-Programmer Ver. 5.0

 

 

(Model: WS02-CXPC1-E-V50). It cannot be installed for the CX-Programmer

 

 

Ver. 4.0 or earlier. To connect the FQM1 and a personal computer, use the

 

 

cables shown in the following table.

 

 

 

 

 

Name

Model

Specifications

 

 

 

Programming Device

CS1W-CN118

Connects a personal computer (Microsoft Windows OS).

Connecting Cables

 

D-Sub 9-pin receptacle (converts between RS-232C and peripheral com-

(for peripheral port)

 

 

munications)

 

 

 

 

 

 

(Length: 0.1 m)

 

 

 

 

 

 

CS1W-CN226

Connects a personal computer (Microsoft Windows OS).

 

 

 

D-Sub 9-pin (Length: 2.0 m)

 

 

 

 

 

 

CS1W-CN626

Connects a personal computer (Microsoft Windows OS).

 

 

 

D-Sub 9-pin (Length: 6.0 m)

 

 

 

Programming Device

XW2Z-200S-CV

Connects a personal computer (Microsoft Windows OS).

Connecting Cables

 

D-Sub 9-pin (Length: 2.0 m), Static-resistant connector used.

(for RS-232C port)

 

 

 

XW2Z-500S-CV

Connects a personal computer (Microsoft Windows OS).

 

 

 

 

 

D-Sub 9-pin (Length: 5.0 m), Static-resistant connector used.

 

 

 

 

 

 

XW2Z-200S-V

Connects a personal computer (Microsoft Windows OS).

 

 

 

D-Sub 9-pin (Length: 2.0 m) (see note)

 

 

 

 

 

 

XW2Z-500S-V

Connects a personal computer (Microsoft Windows OS).

 

 

 

D-Sub 9-pin (Length: 5.0 m) (see note)

 

 

 

USB-Serial Conver-

CS1W-CIF31

USB to D-Sub 9-pin conversion cable

sion Cable

 

(Length: 0.5 m)

Note These RS-232C Connecting Cables cannot be used to connect to the CX- Programmer with Peripheral Bus communications. Connect to the CX-Pro- gramer with Host Link (SYSMAC WAY) communications.

!Caution Never connect a PLC Programming Console (such as the C200H-PRO27) to the Coordinator Module’s peripheral port. The FQM1 may malfunction if a PLC Programming Console is connected.

234

Page 257
Image 257