Omron FQM1-MMA21 Built-inI/O Allocations, Allocations Directly Related to Instructions

Models: FQM1-MMP21 FQM1-MMA21 FQM1-CM001

1 414
Download 414 pages 44.52 Kb
Page 370
Image 370
RS-232C Port

System Setup, Auxiliary Area Allocations, and Built-in I/O Allocations

Appendix C

RS-232C Port

 

 

 

 

 

 

 

 

Address

Bits

Name

Function

Controlled by

 

 

 

 

 

A410

02 to 05

RS-232C Port Error

Indicates the status of the error flags that turn ON when an error has

Module

 

 

Flags

occurred at the RS-232C port.

 

 

 

 

 

 

 

08

RS-232C Port Commu-

Turns ON when a communications error has occurred at the RS-232C

 

 

 

nications Error Flag

port.

 

 

09

RS-232C Port Send

Turns ON when the RS-232C port is ready to send data in no-protocol

 

 

 

Ready Flag (no-protocol

mode.

 

 

 

mode)

 

 

 

10

RS-232C Port Recep-

Turns ON when the RS-232C port has completed the reception in no-

 

 

 

tion Completed Flag

protocol mode.

 

 

 

(no-protocol mode)

 

 

 

11

RS-232C Port Recep-

Turns ON when a data overflow occurred during reception through the

 

 

 

tion Overflow Flag (no-

RS-232C port in no-protocol mode.

 

 

 

protocol mode)

 

 

 

15

RS-232C Port Settings

Turns ON while the RS-232C port’s communications settings are being

 

 

 

Changing Flag

changed.

 

 

 

 

 

 

A411

00 to 15

RS-232C Port Recep-

Indicates (in binary) the number of bytes of data received when the

 

 

 

tion Counter (no-proto-

RS-232C port is in no-protocol mode.

 

 

 

col mode)

 

 

 

 

 

 

 

A502

00

RS-232C Port Restart

Turn this bit ON to restart the RS-232C port.

User

 

 

Bit

This bit is turned OFF automatically when the restart processing is

 

 

 

 

 

 

 

 

completed.

 

 

 

 

 

 

RS-422A Port

 

 

 

 

 

 

 

 

Address

Bits

Name

Function

Controlled by

 

 

 

 

 

A414

02 to 05

RS-422A Port Error

Indicates the status the error flags that turn ON when an error has

Module

 

 

Flags

occurred at the RS-422A port.

 

 

 

 

 

 

 

08

RS-422A Port Commu-

Turns ON when a communications error has occurred at the RS-422A

 

 

 

nications Error Flag

port.

 

 

09

RS-422A Port Send

Turns ON when the RS-422A port is ready to send data in no-protocol

 

 

 

Ready Flag (no-protocol

mode.

 

 

 

mode)

 

 

 

10

RS-422A Port Recep-

Turns ON when the RS-422A port has completed the reception in no-

 

 

 

tion Completed Flag

protocol mode.

 

 

 

(no-protocol mode)

 

 

 

11

RS-422A Port Recep-

Turns ON when a data overflow occurred during reception through the

 

 

 

tion Overflow Flag (no-

RS-422A port in no-protocol mode.

 

 

 

protocol mode)

 

 

 

15

RS-422A Port Settings

Turns ON while the RS-422A port’s communications settings are being

 

 

 

Changing Flag

changed.

 

 

 

 

 

 

A415

00 to 15

RS-422A Port Recep-

Indicates (in binary) the number of bytes of data received when the

 

 

 

tion Counter (no-proto-

RS-422A port is in no-protocol mode.

 

 

 

col mode)

 

 

 

 

 

 

 

A502

02

RS-422A Port Restart

Turn this bit ON to restart the RS-422A port.

User

 

 

Bit

This bit is turned OFF automatically when the restart processing is

 

 

 

 

 

 

 

 

completed.

 

 

 

 

 

 

Allocations Directly Related to Instructions

 

 

 

 

 

 

Address

Bits

Name

Function

Controlled by

A200

11

First Cycle Flag

ON for one cycle after FQM1 operation begins.

Module

 

 

 

 

 

 

12

Step Flag

ON for one cycle when step execution is started with STEP(008).

 

 

 

 

 

 

A510 to

00 to 15

Macro Area Input Words

Before the subroutine specified in MCRO(099) is executed, the con-

 

A514

 

 

tents of the five words specified in the operand to be passed to the

 

 

 

 

subroutine are stored here.

 

 

 

 

 

 

A515 to

00 to 15

Macro Area Output

After the subroutine specified in MCRO(099) has been executed, the

 

A519

 

Words

results of the subroutine are transferred to these five words.

 

Built-in I/O Allocations

The Coordinator Module and Motion Control Modules all have built-in I/O. The I/O Area allocations to the con- tacts on the Modules are given in the following tables.

347

Page 370
Image 370
Omron FQM1-MMA21 Built-inI/O Allocations, Allocations Directly Related to Instructions, Appendix C, RS-232CPort