Omron FQM1-MMA21, FQM1-CM001, FQM1-MMP21 Serial Communications, Section, FINS Commands

Models: FQM1-MMP21 FQM1-MMA21 FQM1-CM001

1 414
Download 414 pages 44.52 Kb
Page 151
Image 151
FINS Commands

Serial Communications

 

Section 6-1

 

 

 

 

Type

Header

Name

Function

 

code

 

 

 

 

 

 

Program area

RP

PROGRAM READ

Reads the contents of the Coordinator Module’s user program

access com-

 

 

area in machine language (object code).

mands

 

 

 

WP

PROGRAM WRITE

Writes the machine language (object code) program transmit-

 

 

 

 

ted from the host computer into the Coordinator Module’s user

 

 

 

program area.

 

 

 

 

Compound

QQMR

COMPOUND COMMAND

Registers the desired bits and words in a table.

reading of I/O

 

 

 

QQIR

COMPOUND READ

Reads the registered words and bits from I/O memory.

memory

 

 

 

Processing Host

XZ

ABORT (command only)

Aborts the Host Link command that is currently being pro-

Link communi-

 

 

cessed.

cations

 

 

 

**

INITIALIZE (command

Initializes the transmission control procedure of all Host Link

 

 

 

only)

Units connected to the host computer.

 

 

 

 

 

IC

Undefined command

This response is returned if the header code of a command

 

 

(response only)

was not recognized.

 

 

 

 

FINS Commands

The following table lists the FINS commands. Refer to the C-series Host Link Units System Manual (W143) for details.

Type

Command

Name

Function

 

 

code

 

 

 

 

 

 

 

I/O Memory

01

 

01

MEMORY AREA READ

Reads consecutive data from the I/O memory area.

Area Access

 

 

 

 

 

01

 

02

MEMORY AREA WRITE

Writes consecutive data to the I/O memory area.

 

 

 

 

 

 

 

 

 

01

 

03

MEMORY AREA FILL

Fills the specified range of I/O memory with the same

 

 

 

 

 

data.

 

 

 

 

 

 

 

01

 

04

MULTIPLE MEMORY AREA

Reads non-consecutive data from the I/O memory area.

 

 

 

 

READ

 

 

 

 

 

 

 

 

01

 

05

MEMORY AREA TRANSFER

Copies and transfers consecutive data from one part of

 

 

 

 

 

the I/O memory area to another.

 

 

 

 

 

 

Parameter

02

 

01

PARAMETER AREA READ

Reads consecutive data from the parameter area.

Area Access

 

 

 

 

 

02

 

02

PARAMETER AREA WRITE

Writes consecutive data to the parameter area.

 

 

 

 

 

 

 

 

 

02

 

03

PARAMETER AREA FILL

Fills the specified range of the parameter area with the

 

 

 

 

 

same data.

 

 

 

 

 

 

Program Area

03

 

06

PROGRAM AREA READ

Reads data from the user program area.

Access

 

 

 

 

 

03

 

07

PROGRAM AREA WRITE

Writes data to the user program area.

 

 

 

 

 

 

 

 

 

03

 

08

PROGRAM AREA CLEAR

Clears the specified range of the user program area.

 

 

 

 

 

 

Execution

04

 

01

RUN

Switches the Coordinator Module to RUN or MONITOR

Control

 

 

 

 

mode.

 

 

 

 

 

 

 

04

 

02

STOP

Switches the Coordinator Module to PROGRAM mode.

 

 

 

 

 

 

Configuration

05

 

01

CONTROLLER DATA READ

Reads Coordinator Module information.

Read

 

 

 

 

 

05

 

02

CONNECTION DATA READ

Reads the model numbers of the specified Units.

 

 

 

 

 

 

 

 

Status Read

06

 

01

CONTROLLER STATUS READ

Reads the Coordinator Module’s status information.

 

 

 

 

 

 

 

06

 

20

CYCLE TIME READ

Reads the average, maximum, and minimum cycle

 

 

 

 

 

times.

 

 

 

 

 

 

Message

09

 

20

MESSAGE READ/CLEAR

Reads/clears messages and FAL(S) messages.

Access

 

 

 

 

 

 

 

 

 

 

 

Access Right

0C

 

01

ACCESS RIGHT ACQUIRE

Acquires the access right if no other device holds it.

 

 

 

 

 

 

 

0C

 

02

ACCESS RIGHT FORCED

Acquires the access right even if another device cur-

 

 

 

 

ACQUIRE

rently holds it.

 

 

 

 

 

 

 

0C

 

03

ACCESS RIGHT RELEASE

Releases the access right regardless of what device

 

 

 

 

 

holds it.

 

 

 

 

 

 

Error Access

21

 

01

ERROR CLEAR

Clears errors and error messages.

 

 

 

 

 

 

 

21

 

02

ERROR LOG READ

Reads the error log.

 

 

 

 

 

 

 

21

 

03

ERROR LOG CLEAR

Clears the error log pointer to zero.

 

 

 

 

 

 

128

Page 151
Image 151
Omron FQM1-MMA21, FQM1-CM001, FQM1-MMP21 operation manual Serial Communications, Section, FINS Commands