Omron FQM1-MMP21, FQM1-CM001, FQM1-MMA21 I/O Memory, Appendix B, Using the Clock Pulses

Models: FQM1-MMP21 FQM1-MMA21 FQM1-CM001

1 414
Download 414 pages 44.52 Kb
Page 332
Image 332
Clock Pulses

I/O Memory

Appendix B

Clock Pulses

The Clock Pulses are flags that are turned ON and OFF at regular intervals by the system.

Name

Label

CX-Programmer

 

 

Operation

 

 

Symbol

 

 

 

0.02 s Clock Pulse

0.02s

P_0_02s

0.01 s

 

ON for 0.01 s

 

 

 

 

OFF for 0.01 s

 

 

 

 

 

 

 

 

0.01 s

 

 

0.1 s Clock Pulse

0.1s

P_0_1s

0.05 s

 

ON for 0.05 s

 

 

 

 

OFF for 0.05 s

 

 

 

 

 

 

 

 

0.05 s

 

 

0.2 s Clock Pulse

0.2s

P_0_2s

0.1 s

 

ON for 0.1 s

 

 

 

 

OFF for 0.1 s

 

 

 

 

 

 

 

 

0.1 s

 

 

1 s Clock Pulse

1s

P_1s

0.5 s

 

ON for 0.5 s

 

 

 

 

OFF for 0.5 s

 

 

 

 

 

 

 

 

0.5 s

 

 

1 min Clock Pulse

1min

P_1min

 

30 s

ON for 30 s

 

 

 

 

OFF for 30 s

 

 

 

 

 

30 s

The Clock Pulses are specified with labels (or symbols) rather than addresses.

Note The CX-Programmer treats Clock Pulses as global symbols beginning with P_.

The Clock Pulses are read-only; they cannot be overwritten from instructions or the CX-Programmer. The Clock Pulses are cleared at the start of operation.

Using the Clock Pulses

The following example turns CIO 0001.00 ON and OFF at 0.5 s intervals.

1 s

0001.00

 

 

 

0.5 s

0001.00

0.5 s

Instruction

Operand

LD

1 s

OUT

0001.00