Omron FQM1-MMP21, FQM1-CM001, FQM1-MMA21 Analog Input Functions, Section, Auxiliary Area, A550

Models: FQM1-MMP21 FQM1-MMA21 FQM1-CM001

1 414
Download 414 pages 44.52 Kb
Page 242
Image 242
A550

Analog Input Functions

 

 

 

Section 7-9

Auxiliary Area

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Word

Bits

 

Function

 

Settings

Controlled

 

 

 

 

 

 

 

 

by

 

 

 

 

 

 

A550

00 to 15

 

Analog Input PV

Contains the value input from the analog input port

Motion

 

 

 

 

 

(using either the END refresh or immediate refresh)

Control

 

 

 

 

 

in 4-digit hexadecimal.

 

Module

 

 

 

 

 

The PV range depends on the input range:

 

 

 

 

 

 

• 0 to 10 V:

FE70 to 20D0 hex

 

 

 

 

 

 

• 0 to 5 V or 1 to 5 V:

FF38 to 1068 hex

 

 

 

 

 

 

10 to 10 V:

DDA0 to 2260 hex

 

 

 

 

 

 

 

 

 

A552

00

 

Analog Input

Analog Input

User Adjustment

OFF: Not adjusted

 

 

 

 

Status

 

Completed

ON:

Adjustment completed

 

 

 

 

 

 

 

 

 

 

 

01 to 06

 

 

 

Reserved

 

 

 

 

 

 

 

 

 

 

 

 

07

 

 

 

Analog Sampling

OFF: Not started

 

 

 

 

 

 

Started

ON:

Started

 

 

 

 

 

 

 

 

 

 

08

 

 

 

Factory Adjustment

OFF: No Error

 

 

 

 

 

 

Data Error

ON:

Error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Checked at startup.)

 

 

 

 

 

 

 

 

 

 

09

 

 

 

User Adjustment

OFF: No Error

 

 

 

 

 

 

Data Error

ON:

Error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Checked at startup.)

 

 

 

 

 

 

 

 

 

 

 

10 to 14

 

Reserved

 

 

 

 

---

 

 

 

 

 

 

 

 

 

15

 

Analog Input

Analog Input

Analog Sampling

OFF: Normal sampling

Motion

 

 

 

Status

 

Overlap

ON:

The next sampling

Control

 

 

 

 

 

 

Module

 

 

 

 

 

 

 

operation occurred

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

before the present

 

 

 

 

 

 

 

 

sampling operation

 

 

 

 

 

 

 

 

completed.

 

 

 

 

 

 

 

 

 

A559

01 to 15

 

Analog Input

Analog Input

Number of Samples

Indicates the number of data

Motion

 

 

 

Status

 

 

samples actually input since

Control

 

 

 

 

 

 

sampling started.

Module

 

 

 

 

 

 

 

 

A560

00 to 15

 

Analog Out-

When an END refresh is selected, the 4-digit hexadecimal value set

With imme-

 

 

 

put 1 Output

here by the user is output from analog output port 1.

diate

 

 

 

Value

When immediate refreshing is selected, the 4-digit hexadecimal value

refresh:

 

 

 

 

Motion

 

 

 

 

being output from analog output port 1 is stored here for monitoring.

 

 

 

 

Control

 

 

 

 

The output value range depends on the output range, as shown below.

 

 

 

 

• 0 to 10 V, 0 to 5 V or 1 to 5 V: FF38 to 1068 hex

Module

 

 

 

 

With END

 

 

 

 

10 to 10 V: EA84 to 157C hex

 

 

 

 

 

 

 

 

refresh:

 

 

 

 

Note

 

 

 

 

 

 

 

 

 

 

User

 

 

 

 

1. Set the analog output method (END or immediate refreshing) with the

 

 

 

 

 

System Setup’s output method setting. A setting of 0 hex specifies an

 

 

 

 

 

END refresh. This setting applies to both analog output 1 and 2.

 

 

 

 

 

2. Specify the output range with the output 1 setting.

 

 

 

 

 

 

 

A561

00 to 15

 

Analog Out-

This word has the same settings as the analog output 1 output value

 

 

 

 

put 2 Output

(A560), above. (When an END refresh is selected, set the value to out-

 

 

 

 

Value

put from analog output port 2. When an immediate refresh is selected,

 

 

 

 

 

the output value is stored here for monitoring.)

 

 

 

 

 

 

Note

 

 

 

 

 

 

 

 

1. Set the analog output method (END or immediate refresh) with the

 

 

 

 

 

System Setup’s output method setting. A setting of 0 hex specifies an

 

 

 

 

 

END refresh. This setting applies to both analog output 1 and 2.

 

 

 

 

 

2. Specify the output range with the output 2 setting.

 

 

 

 

 

 

 

 

 

 

219

Page 242
Image 242
Omron FQM1-MMP21, FQM1-CM001, FQM1-MMA21 operation manual Analog Input Functions, Section, Auxiliary Area, A550