Auxiliary Area Allocations

 

Appendix D

 

 

 

 

 

Address

Bits

Name

 

Function

 

 

 

 

 

A559

00 to 15

Number of Analog Samples

 

Indicates the number of data samples actually input since sam-

 

 

 

 

pling started.

A560

00 to 15

Analog Output 1 Output Value

 

When an END refresh is selected, the 4-digit hexadecimal value

 

 

 

 

set here by the user is output from analog output port 1.

 

 

 

 

When immediate refreshing is selected, the 4-digit hexadecimal

 

 

 

 

value being output from analog output port 1 is stored here for

 

 

 

 

monitoring. The output value range depends on the output range,

 

 

 

 

as shown below.

 

 

 

 

• 0 to 10 V, 0 to 5 V or 1 to 5 V: FF38 to 1068 hex

 

 

 

 

10 to 10 V: EA84 to 157C hex

 

 

 

 

Note

 

 

 

 

1. Set the analog output method (END or immediate refreshing)

 

 

 

 

with the System Setup’s output method setting. A setting of 0

 

 

 

 

hex specifies an END refresh. This setting applies to both ana-

 

 

 

 

log output 1 and 2.

 

 

 

 

2. Specify the output range with the output 1 setting.

 

 

 

 

 

A561

00 to 15

Analog Output 2 Output Value

 

This word has the same settings as the analog output 1 output

 

 

 

 

value (A560), above. (When an END refresh is selected, set the

 

 

 

 

value to output from analog output port 2. When an immediate

 

 

 

 

refresh is selected, the output value is stored here for monitoring.)

 

 

 

 

Note

 

 

 

 

1. Set the analog output method (END or immediate refresh) with

 

 

 

 

the System Setup’s output method setting. A setting of 0 hex

 

 

 

 

specifies an END refresh. This setting applies to both analog

 

 

 

 

output 1 and 2.

 

 

 

 

2. Specify the output range with the output 2 setting.

 

 

 

 

 

A562

00

Analog Output 1 Flags

User Adjustment

Initial value is 0.

 

 

 

Completed

Set to 1 if user performs offset/gain adjustment and Returns to

 

 

 

 

factory default setting of 0 if adjustment value is cleared.

 

04

 

Operating

ON: ON while the analog output is being changed by ACC(888).

 

 

 

 

OFF: Turned OFF when target value is reached.

 

 

 

 

 

 

08

 

Output SV Error

ON: ON when the output SV setting is outside of the allowed set-

 

 

 

 

ting range.

 

 

 

 

OFF: OFF when the output SV is within range.

 

 

 

 

 

 

12

 

Factory Adjust-

ON: ON when the factory-set data stored in flash memory is

 

 

 

ment Value

invalid.

 

 

 

Error

OFF: OFF when the factory-set data stored in flash memory is

 

 

 

 

normal.

 

 

 

 

 

 

14

 

User Adjustment

ON: ON when the user-set adjustment value stored in flash mem-

 

 

 

Value Error

ory is invalid.

 

 

 

 

OFF: OFF when the user-set adjustment value stored in flash

 

 

 

 

memory is normal.

 

 

 

 

 

A563

00

Analog Output 2 Flags

User Adjustment

Same as for Analog Output 1 Flags.

 

 

 

Completed

 

 

04

 

Operating

 

 

 

 

 

 

 

08

 

Output SV Error

 

 

 

 

 

 

 

12

 

Factory Adjust-

 

 

 

 

ment Value

 

 

 

 

Error

 

 

 

 

 

 

 

14

 

User Adjustment

 

 

 

 

Value Error

 

 

 

 

 

 

A564

00

Analog Output 1 Conversion Enable Bit

ON: Enables D/A conversion (enables analog output).

 

 

 

 

OFF: Disables D/A conversion (analog values output according to

 

 

 

 

Output Stop Function specification in System Setup).

 

 

 

 

Note This bit is cleared when the Modules operating mode is

 

 

 

 

changed between RUN or MONITOR mode and PROGRAM

 

 

 

 

mode.

 

 

 

 

A565

00

Analog Output 2 Conversion Enable Bit

ON: Enables D/A conversion (enables analog output).

 

 

 

 

OFF: Disables D/A conversion (analog values output according to

 

 

 

 

Output Stop Function specification in System Setup).

 

 

 

 

Note This bit is cleared when the Modules operating mode is

 

 

 

 

changed between RUN or MONITOR mode and PROGRAM

 

 

 

 

mode.

353

Page 376
Image 376