Omron FQM1-MMP21, FQM1-CM001 3-2Wiring, Section, AC Power Source, Isolation Transformer

Models: FQM1-MMP21 FQM1-MMA21 FQM1-CM001

1 414
Download 414 pages 44.52 Kb
Page 83
Image 83
Wiring

Wiring

Section 3-2

3-2 Wiring

3-2-1 Wiring Power Supply Units

PA202

AC power supply 100 to 240 V

M4 self-raising screws

AC power supply

Isolation

transformer 1:1

RUN output (See note.)

 

 

ON when Coordinator Module

 

 

is in RUN or MONITOR mode.

Power

OFF when in PROGRAM mode

supply

or during a fatal error.

 

 

POWER

L1

AC100 -240V

INPUT L2/N

NC

NC

Note

The RUN output function is provided only for the CJ1W-PA205R Power Sup-

 

ply Unit. It is not provided on the CJ1W-PA202 Power Supply Unit.

AC Power Source

• Supply 100 to 240 V AC.

 

• Keep the voltage fluctuations within the specified range.

 

 

 

 

 

 

 

Supply voltage

Allowable voltage fluctuations

 

 

 

 

 

 

 

 

100 to 240 V AC

85 to 264 V AC

 

 

 

 

 

 

 

• If one power supply phase of the equipment is grounded, connect the

 

 

grounded phase side to the L2/N terminal.

Isolation Transformer

The FQM1's internal noise isolation circuits are sufficient to control typical

 

noise in power supply lines, but noise between the FQM1 and ground can be

 

significantly reduced by connecting a 1-to-1 isolation transformer. Do not

 

ground the secondary coil of the transformer.

Power Supply Capacity

The power consumption will be 100 VA max. for the CJ1W-PA205R and 50 VA

 

for the CJ1W-PA202, but there will be a surge current of at least 5 times the

 

max. current when the power is turned ON.

60

Page 83
Image 83
Omron FQM1-MMP21, FQM1-CM001, FQM1-MMA21 3-2Wiring, Section, AC Power Source, Isolation Transformer, Power Supply Capacity