9-2-9 Cycle Time Overrun Error Check

Error Processing

Section 9-2

9-2-9 Cycle Time Overrun Error Check

Cycle Time Overrun Error

occurred

Is the assumed

No

 

 

cycle time less than the

 

 

watch cycle time set in the

 

 

 

System Setup?

 

 

 

Yes

 

 

 

Are interrupts

Yes

Is the Max.

No

Interrupt Processing Time

being used?

 

 

 

setting OK?

 

 

 

 

No

 

Yes

 

The program execution time exceeded the watch cycle time. Increase the watch cycle time setting in the System Setup.

It is possible that the error occurred because the interrupt task execution time was too long.

It is possible that the error occurred because two or more interrupt tasks were executed. Check how often interrupt tasks are executed.

There may be an error in the program. Check all tasks, particularly instructions that control loops ,such as the JMP instruction.

Not cause of error

9-2-10 System Setup Error Check

System Setup Error occurred

What is in

the System Setup Error #0154 hex (340) Location (A406)?

Other value

9-2-10 System Setup Error Check Set the proecessing mode correctly.

A communications error may have occurred during the transfer from the CX-Programmer. Transfer the System Setup again.