Omron FQM1-MMA21 Appendix C, Peripheral Port Settings for NT Link, Host Link Unit Number

Models: FQM1-MMP21 FQM1-MMA21 FQM1-CM001

1 414
Download 414 pages 44.52 Kb
Page 337
Image 337
Host Link Unit Number

System Setup, Auxiliary Area Allocations, and Built-in I/O Allocations

Appendix C

Host Link Unit Number

 

 

 

 

 

 

 

 

 

Address

Settings

Function

Related flags and

When setting is

 

 

 

 

words

read

Word

Bits

 

 

 

 

 

 

 

 

 

 

 

 

+147

00 to 07

00 to 1F hex: Unit number 0

This setting determines the Coordinator

A412.15 (Peripheral

At next cycle (Also

 

 

to 31

Module's unit number when it is con-

Port Settings Changing

can be changed

 

 

Default: 00 hex

nected in a 1-to-N (N=2 to 32) Host

Flag)

with STUP (237).)

 

 

 

Link.

 

 

Peripheral Port Settings for NT Link

 

 

Serial Communications Mode

 

 

 

 

 

 

 

 

Address

Settings

Function

Related flags and

When setting is

 

 

 

 

words

read

Word

Bits

 

 

 

 

 

 

 

 

 

 

 

 

+144

08 to 11

02 hex: NT Link

This setting determines whether the

A412.15 (Peripheral

At next cycle (Also

 

 

Default: 0 hex

peripheral port will operate in NT Link

Port Settings Changing

can be changed

 

 

 

mode or another serial communications

Flag)

with STUP (237).)

 

 

 

mode. Set 02 for NT Link Mode.

 

 

 

 

 

Note Communications will not be pos-

 

 

 

 

 

sible with PTs set for 1:1 NT Links.

 

 

Baud Rate

 

 

 

 

 

 

 

 

 

Address

Settings

Function

Related flags and

When setting is

 

 

 

 

words

read

Word

Bits

 

 

 

 

 

 

 

 

 

 

 

 

+145

00 to 07

08 hex: Standard NT Link

Only the standard setting of 38,400 can

A412.15 (Peripheral

At next cycle (Also

 

 

Default: 00 hex

be used for the NT Link Serial Commu-

Port Settings Changing

can be changed

 

 

 

nications Mode.

Flag)

with STUP (237).)

Maximum Unit Number for NT Link (NT Link Max.)

 

 

 

 

 

 

 

Address

Settings

Function

Related flags and

When setting is

 

 

 

 

words

read

Word

Bits

 

 

 

 

 

 

+150

00 to 03

0 to 7 hex

This setting determines the highest unit

A412.15 (Peripheral

At next cycle (Also

 

 

Default: 0 hex

number of PT that can be connected to

Port Settings Changing

can be changed

 

 

 

the FQM1.

Flag)

with STUP (237).)

Peripheral Port Settings for Peripheral Bus (ToolBus)

Standard/Customer Setting

Address

Settings

Function

Related flags and

When setting is

 

 

 

 

words

read

Word

Bits

 

 

 

 

 

 

 

 

 

 

 

 

+144

15

0: Standard

The standard setting is for 9,600 baud.

A412.15 (Peripheral

At next cycle (Also

 

 

1: Custom

 

Port Settings Changing

can be changed

 

 

Default: 0

 

Flag)

with STUP (237).)

 

 

 

 

 

 

 

 

 

 

 

Serial Communications Mode

Address

Settings

Function

Related flags and

When setting is

 

 

 

 

words

read

Word

Bits

 

 

 

 

 

 

 

 

 

 

 

 

+144

08 to 11

04 hex: Peripheral bus

This setting determines whether the

A412.15 (Peripheral

At next cycle (Also

 

 

Default: 0 hex

peripheral port will operate in Periph-

Port Settings Changing

can be changed

 

 

 

eral Bus Mode or another serial com-

Flag)

with STUP (237).)

 

 

 

munications mode. Set 04 for

 

 

 

 

 

Peripheral Bus Mode.

 

 

 

 

 

Peripheral Bus Mode is used to com-

 

 

 

 

 

municate with the CX-Programmer.

 

 

314

Page 337
Image 337
Omron FQM1-MMA21 Appendix C, Peripheral Port Settings for NT Link, Host Link Unit Number, Serial Communications Mode