System Setup, Auxiliary Area Allocations, and Built-in I/O AllocationsAppendix C

FQM1-MMP21 Motion Control Modules with Pulse I/O

CX-Programmer: Pulse Input Tab Page

Address

Bits

 

Function

Remarks

When setting is

 

 

 

 

 

 

read

 

 

 

 

 

 

 

+320

00 to 03

High-speed

 

Input method

0 hex: Phase differential x1

At power ON

 

 

counter 1 (Counter

 

1 hex: Phase differential x2

 

 

 

1)

 

 

2 hex: Phase differential x4

 

 

 

 

 

 

 

 

 

 

 

 

3 hex: Increment/decrement pulse inputs

 

 

 

 

 

 

4 hex: Pulse + direction inputs

 

 

 

 

 

 

 

 

 

04 to 07

 

 

Reset method

0 hex: Software reset

 

 

 

 

 

 

1 hex: Phase Z and software reset

 

 

 

 

 

 

 

 

 

08 to 11

 

 

Counting speed

0 hex: 50 kHz

 

 

 

 

 

 

1 hex: 500 kHz

 

 

 

 

 

 

 

 

 

12 to 15

 

 

Counter operating

0 hex: Linear counter

 

 

 

 

 

mode (Counter opera-

1 hex: Circular counter

 

 

 

 

 

tion)

2 hex: Absolute linear counter (CW)

 

 

 

 

 

 

 

 

 

 

 

 

3 hex: Absolute circular counter

 

 

 

 

 

 

4 hex: Absolute linear counter (CW+)

 

 

 

 

 

 

Note When setting any mode except for a linear

 

 

 

 

 

 

counter (0 hex), be sure to set the Circular Maxi-

 

 

 

 

 

 

mum Count/Absolute Encoder Resolution.

 

+321

00 to 03

 

 

Counter data to moni-

0 hex: Do not monitor (Non-monitor)

 

 

 

 

 

tor (Counter data dis-

1 hex: Counter PV changes (Counter movements

 

 

 

 

 

play)

(mode 1))

 

 

 

 

 

 

2 hex: Frequency (mode 2)

 

 

 

 

 

 

Note The frequency (mode 2) can be set only for

 

 

 

 

 

 

high-speed counter 1.

 

 

 

 

 

 

 

 

 

04 to 15

 

 

Reserved

 

 

 

 

 

 

 

 

 

+322

00 to 15

 

 

Sampling time (for

Sets the sampling time for monitoring counter PV

 

 

 

 

 

mode 1 only)

changes (mode 1)

 

 

 

 

 

 

0000: Cycle time

 

 

 

 

 

 

0001 to 270F hex: 1 to 9,999 ms

 

 

 

 

 

 

(unit: 1 ms)

 

 

 

 

 

 

Note This setting is valid only when the Counter

 

 

 

 

 

 

Data Display (bits 00 to 03 of +321) is set to 1 hex

 

 

 

 

 

 

(mode 1).

 

 

 

 

 

 

 

 