Omron FQM1-MMA21, FQM1-CM001, FQM1-MMP21 Section, Pulse Outputs with Acceleration/Deceleration

Models: FQM1-MMP21 FQM1-MMA21 FQM1-CM001

1 414
Download 414 pages 44.52 Kb
Page 208
Image 208
Pulse Outputs with Acceleration/Deceleration

Pulse Outputs

Section 7-6

Set the clock speed for pulse outputs 1 and 2.

4.Create the necessary ladder programming.

Use PULS(886) to set number of output pulses for the specified port.

Use SPED(885) to start pulse output control without acceleration/deceler- ation from the specified port.

Use INI(880) to stop pulse output from the specified port.

Use PRV(881) to read the pulse output PV of the specified port.

Pulse output function

System Setup

Pulse output mode

 

 

 

Single-phase output

 

 

 

 

without acceleration/

 

 

 

 

deceleration

 

 

 

 

(fixed duty ratio)

 

 

 

 

 

 

 

 

 

Ladder program

 

 

 

PULS

 

 

SET PULSES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set the number of

 

 

 

INI

 

 

output pulses.

 

 

 

 

 

 

 

 

 

 

 

MODE CONTROL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stop pulse output.

 

 

 

 

 

 

 

 

SPED

Start output

Ladder program

SPEED OUTPUT

Output mode:

CW/CCW, independent/continuous

Target frequency

Start pulse output

CW

CCW

CW

CCW

Pulse output port 1

Pulse output port 2

Refresh status (once each cycle

Refresh PV (once each cycle)

just after instruction execution)

 

 

 

 

Pulse output status

 

Pulse output PV

 

 

 

 

 

 

 

Port 1

A624

 

Port 1

 

A621

A620

Port 2

A625

 

Port 2

 

A623

A622

 

 

 

 

 

 

 

Pulse Outputs with Acceleration/Deceleration

This procedure shows how to use PULS(886) and ACC(888) to generate a pulse output with acceleration or deceleration. The number of output pulses cannot be changed during positioning.

1,2,3... 1. Determine pulse output port.

Select pulse output 1 or 2.

2.Wire the output.

Output: CW and CCW

Output power supply: 5 V DC

3.Make the necessary System Setup settings (Pulse Output Tab Page Op- eration Mode).

Set the pulse output operation mode (in the Pulse Output Tab Page Operation Mode) to relative pulse output, absolute linear pulse output, or absolute circular pulse output.

Set the clock speed for pulse outputs 1 and 2.

4.Create the necessary ladder programming.

Use PULS(886) to set number of output pulses for the specified port.

Use ACC(888) to start pulse output control with acceleration or decelera- tion from the specified port (acceleration and deceleration are specified separately).

Use INI(880) to stop pulse output from the specified port.

185

Page 208
Image 208
Omron FQM1-MMA21, FQM1-CM001, FQM1-MMP21 operation manual Section, Pulse Outputs with Acceleration/Deceleration