Wiring

Section 3-2

Connection Example to Programmable Terminal (PT)

Direct Connection from RS-232C to RS-232C

PTRS-232C port

RS-232C

1:N NT Link

Coordinator Unit

Signal Pin

No.

FG Shell

FG 1

RS-232C SD 2 interface RD 3

RS 4 CS 5

5V 6 DR 7 ER 8 SG 9

9-pin D-sub (male)

PT

Pin Signal

No.

Shell FG

1

2SD RS-232C

3RD interface

4RS

5CS

65V

7

8

9SG

9-pin D-sub (male)

Communications Mode: NT Link (1:N, N = 1 node only)

OMRON Cables with Connectors: XW2Z200T (2 m) XW2Z500T (5 m)

RS-232C Port Specifications

Item

Specification

 

 

Communications method

Half duplex

 

 

Synchronization

Asynchronous

 

 

Baud rate

0.3, 0.6, 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, or 57.6 kbps

 

(See note.)

 

 

Transmission distance

15 m max.

 

 

Interface

EIA RS-232C

 

 

Protocol

Host Link, 1:N NT Link, No-protocol, or Peripheral Bus

 

(Toolbus)

 

 

Note Baud rates for the RS-232C are specified only up to 19.2 kbps. The FQM1 supports serial communications from 38.4 kbps to 57.6 kbps, but some com- puters cannot support these speeds. Lower the baud rate if necessary.