System Setup, Auxiliary Area Allocations, and Built-in I/O Allocations

Appendix C

Host Link Unit Number

 

 

 

 

 

 

 

 

 

Address

Settings

Function

Related flags and

When setting is

 

 

 

 

words

read

Word

Bits

 

 

 

 

 

 

 

 

 

 

 

 

+163

00 to 07

00 to 1F hex: 0 to 31

This setting determines the Coordinator

A410.15 (RS-232C Port

At next cycle (Also

 

 

Default: 00 hex

Module's unit number when it is con-

Settings Changing Flag)

can be changed

 

 

 

nected in a 1-to-N (N=2 to 32) Host

 

with STUP (237).)

 

 

 

Link.

 

 

RS-232C Port Settings for NT Link

 

 

Serial Communications Mode

 

 

 

 

 

 

 

 

Address

Settings

Function

Related flags and

When setting is

 

 

 

 

words

read

Word

Bits

 

 

 

 

 

 

+160

08 to 11

02 hex: NT Link

This setting determines whether the

A410.15 (RS-232C Port

At next cycle (Also

 

 

Default: 00 hex

RS-232C port will operate in NT Link

Settings Changing Flag)

can be changed

 

 

 

mode or another serial communications

 

with STUP (237).)

 

 

 

mode. Set 02 for NT Link Mode.

 

 

 

 

 

Note Communications will not be pos-

 

 

 

 

 

sible with PTs set for 1:1 NT Links.

 

 

Baud Rate

 

 

 

 

 

 

 

 

 

Address

Settings

Function

Related flags and

When setting is

 

 

 

 

words

read

Word

Bits

 

 

 

 

 

 

 

 

 

 

 

 

+161

00 to 07

08 hex: Standard setting

Only the standard setting of 38,400 can

A410.15 (RS-232C Port

At next cycle (Also

 

 

Default: 00 hex

be used for the NT Link Serial Commu-

Settings Changing Flag)

can be changed

 

 

 

nications Mode.

 

with STUP (237).)

Maximum Unit Number for NT Link (NT Link Max.)

 

 

 

 

 

 

 

Address

Settings

Function

Related flags and

When setting is

 

 

 

 

words

read

Word

Bits

 

 

 

 

 

 

 

 

 

 

 

 

+166

00 to 03

0 to 7 hex

This setting determines the highest unit

A410.15 (RS-232C Port

At next cycle (Also

 

 

Default: 00 hex

number of PT that can be connected to

Settings Changing Flag)

can be changed

 

 

 

the FQM1.

 

with STUP (237).)

RS-232C Port Settings for Peripheral Bus (ToolBus)

Standard/Custom Setting

Address

Settings

Function

Related flags and

When setting is

 

 

 

 

words

read

Word

Bits

 

 

 

 

 

 

 

 

 

 

 

 

+160

15

0: Standard

The standard setting is for 9,600 baud.

A410.15 (RS-232C Port

At next cycle (Also

 

 

1: Custom

 

Settings Changing Flag)

can be changed

 

 

Default: 0

 

 

with STUP (237).)

 

 

 

 

 

 

 

 

 

 

 

Serial Communications Mode

Address

Settings

Function

Related flags and

When setting is

 

 

 

 

words

read

Word

Bits

 

 

 

 

 

 

 

 

 

 

 

 

+160

08 to 11

04 hex: Peripheral bus

This setting determines whether the

A410.15 (RS-232C Port

At next cycle (Also

 

 

Default: 0 hex

RS-232C port will operate in Peripheral

Settings Changing Flag)

can be changed

 

 

 

Bus Mode or another serial communi-

 

with STUP (237).)

 

 

 

cations mode. Set 04 for Peripheral Bus

 

 

 

 

 

Mode.

 

 

 

 

 

Peripheral Bus Mode is used to com-

 

 

 

 

 

municate with the CX-Programmer.

 

 

316

Page 339
Image 339