Omron FQM1-CM001, FQM1-MMA21 Details on System Setup Settings, Appendix C, Startup Mode

Models: FQM1-MMP21 FQM1-MMA21 FQM1-CM001

1 414
Download 414 pages 44.52 Kb
Page 348
Image 348
CX-Programmer: Analog Input/Output Tab Page

System Setup, Auxiliary Area Allocations, and Built-in I/O Allocations

Appendix C

 

 

 

 

 

 

 

 

Address

Bits

Function

 

Remarks

 

When setting

 

 

 

 

 

 

 

is read

+330 to 331

00 to 15

High-speed

Absolute offset

 

8000 0000 to 7FFF FFFF hex

 

Immediately

 

 

counter 1 (Counter

 

 

Application origin when using an absolute encoder.

 

 

 

1)

 

 

 

 

 

+332 to 333

00 to 15

High-speed

Absolute offset

 

Same as high-speed counter 1.

 

 

 

 

counter 2 (Counter

 

 

 

 

 

 

 

2)

 

 

 

 

 

CX-Programmer: Analog Input/Output Tab Page

 

 

 

 

 

 

 

 

Address

Bits

Function

 

Remarks

When setting is read

+350

00 to 03

Analog I/O

Input method

0 hex: END refresh

At power ON

 

 

 

 

1 hex: Immediate refresh (using PRV(881)

 

 

 

 

 

 

instruction)

 

 

 

04 to 07

 

Output method

0 hex: END refresh (Analog value output to

 

 

 

 

 

 

A560 and A561 after executing END(001).)

 

 

 

 

 

 

1 hex: Immediate refresh (using instructions)

 

 

 

 

 

 

(Analog value output when SPED(885) or

 

 

 

 

 

 

ACC(888) is executed.) (A560 and A561 are

 

 

 

 

 

 

used for monitoring.)

 

 

+351

00 to 07

Analog input

Input range

00 hex: 10 to 10 V

At power ON

 

 

 

 

01 hex: 0 to 10 V

 

 

 

 

 

 

02 hex: 1 to 5 V (4 to 20 mA)

 

 

 

 

 

 

03 hex: 0 to 5 V

 

 

+353

00 to 07

Analog output 1

Output range

00 hex: 10 to 10 V

At power ON

 

 

 

 

01 hex: 0 to 10 V

 

 

 

 

 

 

02 hex: 1 to 5 V

 

 

 

 

 

 

03 hex: 0 to 5 V

 

 

 

 

 

 

5A hex: Output disabled (Can be used to

 

 

 

 

 

 

shorten I/O refresh time.) (See note.)

 

 

 

08 to 11

 

Output stop func-

0 hex: Clear

 

 

 

 

 

tion

1 hex: Hold

 

 

 

 

 

 

2 hex: Maximum value

 

 

 

 

 

 

 

 

 

+354

00 to 07

Analog output 2

Output range

Same as for analog output 1.

 

 

 

 

 

 

 

 

 

 

 

08 to 15

 

Output stop func-

 

 

 

 

 

 

 

tion

 

 

 

 

Note Analog outputs that are not being used can be disabled to decrease the cycle time.

Details on System Setup Settings

Startup Mode

This setting determines the operating mode that will be used when the power supply to the Coordinator Module is turned ON.

System Setup mode setting disabled

RUN mode

 

 

System Setup mode setting enabled

Program: PROGRAM mode

 

Monitor:

MONITOR mode

 

Run:

RUN mode

Note The Coordinator Module will start in RUN mode unless the Startup Mode setting in the System Setup is enabled.

Peripheral Port Settings

The standard settings are for Host Link Mode, 1 start bit, 7-bit data, even parity, 2 stop bits, and 9,600 baud. Change the System Setup if any other settings are required.

RS-232C Port Settings (Host Link Port)

The standard settings are for Host Link Mode, 1 start bit, 7-bit data, even parity, 2 stop bits, and 9,600 baud. Change the System Setup if any other settings are required. If no-protocol communications are to be used, be sure to change the frame format.

325

Page 348
Image 348