Omron FQM1-CM001 Troubleshooting Problems in Modules, 9-2-13Environmental Conditions Check

Models: FQM1-MMP21 FQM1-MMA21 FQM1-CM001

1 414
Download 414 pages 44.52 Kb
Page 279
Image 279
Troubleshooting Problems in Modules

Troubleshooting Problems in Modules

Section 9-3

9-2-13 Environmental Conditions Check

Environmental Conditions Check

Is the ambient

No

temperature below

 

55°C? Yes

Is the ambient

No

temperature above

 

 

0°C? Yes

Is the ambient

No

humidity between 10%

 

and 90%?

 

Yes

 

Is noise being

No

 

controlled?

 

Yes

 

Consider using a fan or air conditioner.

Consider using a heater.

Consider using an air conditioner.

Install surge suppressor or other noise-suppressing equipment at noise sources.

Is atmosphere

acceptable?

Yes

End

No (See note.)

Consider installing in a panel or improving the installation location.

Note Prevent exposure to corrosive gases, flammable gases, dust, dirt, salts, metal dust, direct sunlight, water, oils, and chemicals.

9-3

Troubleshooting Problems in Modules

 

Coordinator Module Errors

 

 

 

 

 

 

 

Error condition

Probable cause

Remedy

 

 

 

The Power Supply Unit’s POWER indicator is not lit.

PCB short-circuited or dam-

Replace the Power Supply Unit.

 

 

aged.

 

 

 

 

The RDY indicators on the Modules do not go ON.

The power supply line is faulty

Replace the Power Supply Unit.

 

 

 

The Coordinator Module’s RUN indicator does not go

An error in program is causing a

Correct program

ON.

 

fatal error

 

 

 

 

The Power Supply Unit’s RUN output* does not turn

Internal circuitry of Power Sup-

Replace the Power Supply Unit.

ON.

 

ply Unit is faulty.

 

The Coordinator Module’s RUN indicator is lit.

 

 

(*CJ1W-PA205R Power Supply Unit only)

 

 

 

 

 

Motion Control Module does not operate or does not

The I/O bus is faulty.

Replace the Motion Control

operate properly.

 

Module.

 

 

 

A particular I/O point does not operate.

 

 

 

 

 

Error occurs in 8-point or 16-point units.

 

 

 

 

 

A particular I/O point stays ON.

 

 

 

 

 

None of a particular Module’s I/O points will go ON.

 

 

 

 

 

 

256

Page 279
Image 279
Omron FQM1-CM001, FQM1-MMA21, FQM1-MMP21 Troubleshooting Problems in Modules, 9-2-13Environmental Conditions Check, Section