Analog Input Functions

 

 

 

Section 7-9

 

 

 

 

 

 

 

 

Word

Bits

 

Function

 

Settings

Controlled

 

 

 

 

 

 

 

by

 

 

 

 

 

 

 

A562

00

Analog Out-

 

User Adjustment

Initial value is 0.

Motion

 

 

put 1 Flags

 

Completed

Set to 1 if user performs offset/gain adjustment and

Control

 

 

 

 

 

Returns to factory default setting of 0 if adjustment

Module

 

 

 

 

 

 

 

 

 

 

 

value is cleared.

 

 

 

 

 

 

 

 

 

 

01 to 03

 

 

Reserved

 

 

---

 

 

 

 

 

 

 

 

 

04

 

 

Operating

ON:

ON while the analog output is being changed

Motion

 

 

 

 

 

 

by ACC(888).

Control

 

 

 

 

 

OFF: Turned OFF when target value is reached.

Module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

05 to 07

 

 

Reserved

 

 

---

 

 

 

 

 

 

 

 

 

08

 

 

Output SV Error

ON:

ON when the output SV setting is outside of

Motion

 

 

 

 

 

 

the allowed setting range.

Control

 

 

 

 

 

OFF: OFF when the output SV is within range.

Module

 

 

 

 

 

 

 

 

 

 

 

Note Only in End refresh mode

 

 

 

 

 

 

 

 

 

 

09 to 11

 

 

Reserved

 

 

---

 

 

 

 

 

 

 

 

 

12

 

 

Factory Adjust-

ON:

ON when the factory-set data stored in flash

Motion

 

 

 

 

ment Value Error

 

memory is invalid.

Control

 

 

 

 

 

OFF: OFF when the factory-set data stored in

Module

 

 

 

 

 

 

 

 

 

 

 

 

flash memory is normal.

 

 

 

 

 

 

 

 

 

 

13

 

 

Reserved

 

 

---

 

 

 

 

 

 

 

 

 

14

 

 

User Adjustment

ON:

ON when the user-set adjustment value

Motion

 

 

 

 

Value Error

 

stored in flash memory is invalid.

Control

 

 

 

 

 

OFF: OFF when the user-set adjustment value

Module

 

 

 

 

 

 

 

 

 

 

 

 

stored in flash memory is normal.

 

 

 

 

 

 

 

 

 

 

15

 

 

Reserved

 

 

---

 

 

 

 

 

 

 

A563

00

Analog Out-

 

User Adjustment

These flags have the same functions as the Analog

Motion

 

 

put 2 Flags

 

Completed

Output 1 Flags, above.

Control

 

 

 

 

 

 

 

Module

 

01 to 03

 

 

Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

04

 

 

Operating

 

 

 

 

 

 

 

 

 

 

 

 

05 to 07

 

 

Reserved

 

 

 

 

 

 

 

 

 

 

 

 

08

 

 

Output SV Error

 

 

 

 

 

 

 

 

 

 

 

 

09 to 11

 

 

Reserved

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

Factory Adjust-

 

 

 

 

 

 

 

ment Value Error

 

 

 

 

 

 

 

 

 

 

 

 

13

 

 

Reserved

 

 

 

 

 

 

 

 

 

 

 

 

14

 

 

User Adjustment

 

 

 

 

 

 

 

Value Error

 

 

 

 

 

 

 

 

 

 

 

 

15

 

 

Reserved

 

 

 

 

 

 

 

 

 

 

 