Omron FQM1-MMA21, FQM1-CM001, FQM1-MMP21 operation manual Auxiliary Area Allocations, Appendix D

Models: FQM1-MMP21 FQM1-MMA21 FQM1-CM001

1 414
Download 414 pages 44.52 Kb
Page 373
Image 373
Auxiliary Area Allocations

Auxiliary Area Allocations

Appendix D

 

 

 

 

 

Address

Bits

 

Name

Function

 

 

 

 

A403

00

UM Error Flag

Turns ON when there is an error in the user memory.

 

 

 

 

 

04

System Setup Error Flag

Turns ON when there is an error in the System Setup in the Coor-

 

 

 

 

dinator Module or Motion Control Module.

 

 

 

 

 

10

Flash Memory Error Flag

Turns ON when the flash memory is physically destroyed.

 

 

 

 

 

13

Analog Offset/Gain Error Flag

Turns ON when there is an error in the analog I/O offset/gain

 

 

 

 

adjustment value in flash memory.

 

 

 

 

 

14

Flash Memory DM Checksum Error Flag

Turns ON when there is an error in the DM Area data backed up

 

 

(Coordinator Module only)

in flash memory in the Coordinator Module.

A404

05

Constant Cycle Time Exceeded Flag

Turns ON when the actual cycle time exceeds the specified con-

 

 

 

 

stant (minimum) cycle time.

 

 

 

 

 

06

Sync Cycle Time Too Long Flag

Turns ON when one of the Modules exceeds the specified sync

 

 

 

 

cycle time. (Coordinator Module only)

 

 

 

 

 

14

Memory Not Held Flag

Turns ON when corruption is found in the check performed after

 

 

 

 

turning ON power in the areas backed up during power interrup-

 

 

 

 

tions (DM Area (Coordinator Module only) and Error Log Area).

 

 

 

 

A405

11

No END Error Flag

ON when there isn’t an END(001) instruction in each program

 

 

 

 

within a task.

 

12

Task Error Flag

ON when a task error has occurred. The following conditions gen-

 

 

 

 

erate a task error.

 

 

 

 

There isn’t a program allocated to the task.

 

 

 

 

 

13

Differentiation Overflow Error Flag

The allowed value for Differentiation Flags which correspond to

 

 

 

 

differentiation instructions has been exceeded.

 

 

 

 

 

14

Illegal Instruction Error Flag

ON when a program that cannot be executed has been stored.

 

 

 

 

 

15

UM Overflow Error Flag

ON when the last address in UM (User Memory) has been

 

 

 

 

exceeded.

 

 

 

 

A408

00 to 15

Error Log Pointer

When an error occurs, the Error Log Pointer (binary) is incre-

 

 

 

 

mented by 1 to indicate the location where the next error will be

 

 

 

 

recorded as an offset from the beginning of the Error Log Area

 

 

 

 

(A100 to A199).

A409

00 to 15

System Setup Error Location

When there is a setting error in the System Setup, the location of

 

 

 

 

that error is written to A409 in 4-digit hexadecimal.

 

 

 

 

 

A410

02

RS-232C

Parity Error Flag

These error flags turn ON when an error has occurred at the RS-

 

 

Port

 

232C port.

 

03

Framing Error Flag

 

Error

 

 

 

 

 

 

04

Flags

Overrun Error Flag

 

 

 

 

 

 

 

05

 

Timeout Error Flag

 

 

 

 

 

 

 

08

RS-232C Port Communications Error Flag

Turns ON when a communications error has occurred at the RS-

 

 

 

 

232C port.

 

 

 

 

 

09

RS-232C Port Send Ready Flag (no-protocol

Turns ON when the RS-232C port is ready to send data in no-pro-

 

 

mode)

 

tocol mode.

 

 

 

 

 

10

RS-232C Port Reception Completed Flag (no-

Turns ON when the RS-232C port has completed the reception in

 

 

protocol mode)

no-protocol mode.

 

11

RS-232C Port Reception Overflow Flag (no-pro-

Turns ON when a data overflow occurred during reception

 

 

tocol mode)

through the RS-232C port in no-protocol mode.

 

 

 

 

 

15

RS-232C Port Settings Changing Flag

Turns ON while the RS-232C port’s communications settings are

 

 

 

 

being changed.

 

 

 

 

A411

00 to 15

RS-232C Port Reception Counter (no-protocol

Indicates (in binary) the number of bytes of data received when

 

 

mode)

 

the RS-232C port is in no-protocol mode.

A412

02

Periph-

Parity Error Flag

These error flags turn ON when an error has occurred at the

 

 

eral Port

 

peripheral port.

 

03

Framing Error Flag

 

Error

 

 

 

 

 

 

04

Flags

Overrun Error Flag

 

 

 

 

 

 

 

05

 

Timeout Error Flag

 

 

 

 

 

 

 

08

Peripheral Port Communications Error Flag

Turns ON when a communications error has occurred at the

 

 

 

 

peripheral port.

 

15

Peripheral Port Settings Changing Flag

Turns ON while the peripheral port’s communications settings are

 

 

 

 

being changed.

350

Page 373
Image 373
Omron FQM1-MMA21, FQM1-CM001, FQM1-MMP21 operation manual Auxiliary Area Allocations, Appendix D