Error Processing

Section 9-2

9-2-12 I/O Check

Start

 

Is the output

No

indicator for CIO 0001.00

 

normal?

 

Yes

 

The I/O check flowchart is based on the following ladder diagram section, assuming that the problem is SOL1 does not turn ON.

(LS1)

(LS1)

CIO 0000.02

CIO 0000.03

 

 

 

 

 

CIO 0001.00

 

 

 

 

 

CIO 0005.00

 

 

SOL1

Check the 0001.00 terminal

 

Wire terminals correctly.

Replace the terminal block

voltage with a multimeter.

 

connector.

 

 

 

 

No

Yes

 

No

Is the output wiring

No

Is the voltage normal?

 

Did the terminal's

 

correct?

contact fail?

 

 

Yes

 

Yes

 

 

 

Disconnect external wiring and

 

 

 

check conduction status, etc.

 

Monitor the ON/OFF status of CIO 0001.00 from the CX- Programmer.

No

Operation normal?

Yes

Yes

Is the voltage normal?

No

Check the SOL1 solenoid.

 

Replace the Module.

 

 

Input indicators

No

for 0000.02 and 0000.03

 

normal?

 

Yes

 

Check voltage at the 0000.02 and 0000.03 terminals with a multimeter.

Check voltage at the 0000.02 and 0000.03 terminals with a multimeter.

No

Is the voltage normal?

Yes

Disconnect external wiring, connect a test input, and check voltage again.

Is the voltage normal?

 

No

 

Is the input wiring

Yes

correct?

 

No

Yes

Yes

Are the terminal

screws loose?

No

 

Did the terminal's

No

 

contact fail?

 

Yes

 

No

Wire terminals correctly.

Tighten terminals screws.

Replace the terminal block

Replace the Module.

Is the voltage normal?

Yes

Check input devices LS1 and LS2.

connector.

Replace the Module. Return to Start of I/O Check.

255

Page 278
Image 278
Omron FQM1-MMP21, FQM1-CM001, FQM1-MMA21 operation manual 12 I/O Check