Sensor

Analog Input Functions

Section 7-9

The PRV(881) instruction can also be used to read the latest analog input value through immediate refreshing. Analog signals can be input from pres- sure sensors, position meters, or sensors that require high-speed input pro- cessing such as a displacement sensors/end-measuring sensors. Consequently, this function allows simple, low-cost pressure control, tension control, or other control applications requiring high-speed mechanical mea- surement (distortion/thickness/length).

Sensor

(pressure, displacement, etc.)

Selected signal range: 10 to +10 V, 0 to 10 V, 0 to 5 V, 1 to 5 V, or

4 to 20 mA

FQM1-MMA21

Motion Control Module

 

 

Immediate

User program

 

A

refreshing

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

PRV

 

High speed input

 

 

 

 

 

 

 

(A/D conversion time:

 

 

 

 

 

40 s)

 

 

 

 

 

 

Stores the data

 

 

 

 

 

 

 

 

 

when instruction

 

 

 

 

is executed.

 

 

 

 

 

 

 

 

I/O memory

Note The analog input responsiveness has been set relatively high to increase the processing speed. The high responsiveness may result in input signal distor- tion by external noise or interference. Take steps to suppress noise if the Motion Control Module is being used in an environment with a lot of noise. When the Motion Control Module’s analog input value is being used, addi- tional noise countermeasures can be added to the program such as using END refreshing and filtering the input values with AVG instructions.

216

Page 239
Image 239
Omron FQM1-MMP21, FQM1-CM001, FQM1-MMA21 operation manual Analog Input Functions, Section, Sensor pressure, displacement, etc