Appendix C

System Setup, Auxiliary Area Allocations,

and Built-in I/O Allocations

Overview of System Setups

A System Setup contains software settings that the user can change to customize FQM1 operation. Module functions are set using its System Setup.

The Coordinator Module and Motion Control Modules all have System Setups, which are set from the CX-Pro- grammer to customize operation for the following types of applications.

Cases when settings must be changed

Setting(s) to be changed

 

 

• When programming the FQM1 for the first time and the Motion Control

Sync Mode

Modules are being programmed before the Coordinator Module.

 

• When editing or debugging the program in a specific Motion Control Mod-

 

ule.

 

• When you want the FQM1 to go into RUN mode or MONITOR mode and

Startup Mode

start operating immediately after startup.

 

• When you want the operating mode to be other than RUN mode when the

 

power is turned ON.

 

When the peripheral port will not be used with the CX-Programmer (periph-

Peripheral Port Settings

eral bus) communications speed auto-detection and will not be used with the

 

default Host Link communications settings, such as 9,600 bps.

 

When the RS-232C port will not be used with the CX-Programmer (periph-

Host Link Port Settings

eral bus) communications speed auto-detection and will not be used with the

 

default Host Link communications settings, such as 9,600 bps.

 

When you want to communicate with a PT via an NT Link.

Peripheral Port Settings or Host Link Port Settings

 

 

You want a constant (minimum) cycle time setting to create a consistent I/O

Cycle Time

refresh cycle or cycle time.

 

You want to set a maximum cycle time other than 50 ms (1 ms to 100 ms).

Watch Cycle Time

 

 

You want to extend peripheral servicing time because peripheral services

Set Time to All Events

are being executed over several cycles, delaying completion of servicing

 

(want to set a specific time rather than a percent of the cycle time).

 

 

 

The addresses given for the settings in the System Setup are not required for actually making the settings. Use the menus of the CX-Programmer Ver. 5.0@.

System Setup in the Coordinator Module

Sync Settings between Modules (CX-Programmer: Module Settings Tab Page)

Allow Writing to User Memory

Address

Settings

Function

Related flags and

When setting is

 

 

 

 

words

read

Word

Bits

 

 

 

 

 

 

 

 

 

 

 

 

+304

00

0: Writing enabled

Sets and releases write-protection for

---

When disabling: At

 

 

1: Writing disabled

the user memory and System Setup.

 

power ON or at

 

 

Default: Writing enabled

 

 

start of operation

 

 

 

 

When enabling:

 

 

 

 

 

 

 

 

 

 

When changed

 

 

 

 

 

 

Prohibit System Interrupt of the Sync Mode

Address

Settings

Function

Related flags and

When setting is

 

 

 

 

words

read

Word

Bits

 

 

 

 

 

 

+304

08

0: Not prohibited

Sets and releases prohibition of system

---

At start of opera-

 

 

1: Prohibited

interrupts during program execution.

 

tion

 

 

Default: Not prohibited

Set to 1: Prohibit coordinating (match-

 

 

 

 

ing) the operation start timings among

 

 

 

 

 

 

 

 

 

 

Modules in Sync Mode.

 

 

 

 

 

 

 

 

311

Page 334