Error ProcessingSection 9-2

Error ProcessingSection 9-2

9-2

Error Processing

 

 

 

 

9-2-1

Error Categories

 

 

 

 

 

 

Errors in the FQM1 can be broadly divided into the following three categories.

 

 

 

 

 

 

Category

Result

 

Indicators

Comments

 

 

 

 

 

 

 

 

 

 

RDY

RUN

ERR

 

 

 

 

 

 

 

 

Standby

 

The FQM1 will not start operation

OFF

OFF

OFF

This status occurs when a faulty

 

 

in RUN or MONITOR mode.

 

 

 

Motion Control Module is con-

 

 

 

 

 

 

nected.

 

 

 

 

 

 

Non-fatal Errors

The FQM1 will continue operating

ON

ON

Flashing

This status indicates a non-fatal

(including FAL)

in RUN or MONITOR mode.

(Green)

(Green)

(Red)

error other than a communications

 

 

 

 

 

 

error.

 

 

 

 

 

 

Fatal Errors

The FQM1 will stop operating in

ON

OFF

ON

This status indicates a fatal error

(including FALS)

RUN or MONITOR mode.

(Green)

 

(Red)

other than a power interruption.

 

 

 

 

 

 

(The indicators will all be OFF when

 

 

 

 

 

 

there is a power interruption.)

 

 

 

 

 

 

 

9-2-2 Error Information

There are basically four sources of information on errors that have occurred:

The LED indicators on the front of the Coordinator and Motion Control Modules

The Auxiliary Area Error Flags

The Auxiliary Area Error Contents Words

The Auxiliary Area Error Code Word

Module Indicators

Auxiliary Area Flags and Words

RDY Error Processing RUN 9-2-1 ERR Error Categories PRPHL 9-2-2 Error Information COMM1 Indicator Status and Error Conditions COMM2 Manual background

RDY: Initialization completed

RUN: Lit when the Modules are in RUN or MONITOR mode.

ERR: Self-diagnostic test Flashing red: Non-fatal error

Lit red: Fatal error

PRPHL: Lit yellow when the Module is communi-

cating through the peripheral port

COMM1: Lit yellow when the Module is commu- nicating through the RS-232C port

COMM2: Lit yellow when the Module is commu- nicating through the RS-422A port

Error Flags

Flags indicating the type of error.

Error Info.

Words providing error information.

Error Code Word (A400)

Error code

A400

A400 contains the error code. (See note.)

Note

Indicator Status and Error Conditions

When two or more errors occur at the same time, the highest (most serious) error code will be stored in A400.

The following table shows the status of the FQM1’s indicators for errors that have occurred in RUN or MONITOR Mode.

Indicator

CPU error

CPU reset

CPU

Fatal error

Non-fatal

Communications error

 

 

 

standby

 

error

 

 

 

 

 

 

 

Peripheral

RS-232C

RS-422A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RDY

OFF

OFF

OFF

ON

ON

ON

ON

ON

 

 

 

 

 

 

 

 

 

RUN

OFF

OFF

OFF

OFF

ON

---

---

---

 

 

 

 

 

 

 

 

 

243