Omron FQM1-MMP21, FQM1-CM001 General Specifications, Section, Power Supply Unit Specifications

Models: FQM1-MMP21 FQM1-MMA21 FQM1-CM001

1 414
Download 414 pages 44.52 Kb
Page 56
Image 56
General Specifications

General Specifications

Section 2-2

Note (1) Disconnect the Power Supply Unit's LG terminal from the GR terminal when testing insulation and dielectric strength. Testing the insulation and dielectric strength with the LG and GR terminals connected will damage internal circuits.

(2)Do not apply more than 600 V when testing the dielectric strength of an- alog I/O terminals. Applying more than 600 V may damage the internal elements.

Power Supply Unit Specifications

Item

Specifications

 

 

 

Power Supply Unit

CJ1W-PA205R

CJ1W-PA202

 

 

 

Supply voltage

100 to 240 V AC (wide-range), 50/60 Hz

 

 

 

 

Operating voltage

85 to 264 V AC, 47 to 63 Hz

 

and frequency

 

 

ranges

 

 

 

 

 

Power consumption

100 VA max.

50 VA max.

 

 

 

Inrush current

At 100 to 120 V AC:

At 100 to 120 V AC:

(See note 1.)

15 A/8 ms max. for cold start at room temperature

20 A/8 ms max. for cold start at room temperature

 

At 200 to 240 V AC:

At 200 to 240 V AC:

 

30 A/8 ms max. for cold start at room temperature

40 A/8 ms max. for cold start at room temperature

 

 

 

Output capacity

5.0 A, 5 VDC (including supply to Modules)

2.8 A, 5 VDC (including supply to Modules)

 

 

 

 

0.8 A, 24 VDC

0.4 A, 24 VDC

 

 

 

 

Total 25 W max.

Total 14 W max.

 

 

 

Output terminal

Not provided.

 

 

 

 

RUN output

Contact configuration: SPST-NO

Not provided.

 

Switching capacity:

 

 

250 V AC, 2 A (resistive load)

 

 

120 V AC, 0.5 A (inductive load)

 

 

24 VDC, 2 A (resistive load)

 

 

24 VDC, 2 A (inductive load)

 

 

 

 

Insulation resis-

20 Mmin. (at 500 VDC) between AC external and GR terminals (See note 2.)

tance

 

 

 

 

Dielectric strength

2,300 V AC 50/60 Hz for 1 min between AC external and GR terminals (See note 2.)

 

Leakage current: 10 mA max.

 

 

 

 

1,000 V AC 50/60 Hz for 1 min between DC external and GR terminals (See note 1.)

 

Leakage current: 10 mA max.

 

 

 

Noise immunity

2 kV on power supply line (conforming to IEC61000-4-4)

 

 

Vibration resistance

10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s2 in X, Y, and Z directions for 80

 

minutes total (Time coefficient: 8 minutes coefficient factor 10 = total time 80 min.) (conforming to

 

JIS C0040)

 

 

 

Shock resistance

147 m/s2 3 times each in X, Y, and Z directions (conforming to JIS C0041)

Ambient operating

0 to 55°C

 

temperature

 

 

 

 

 

Ambient operating

10% to 90% (with no condensation)

 

humidity

 

 

 

 

 

Atmosphere

Must be free from corrosive gases.

 

 

 

 

Ambient storage

20 to 75°C

 

temperature

 

 

 

 

 

Grounding

Less than 100

 

 

 

 

Enclosure

Mounted in a panel.

 

 

 

 

Weight

5 kg. total max.

 

 

 

 

Dimensions

80 90 65 mm (W H D)

45 90 65 mm (W H D)

 

 

 

Safety measures

Conforms to cULus and EC Directives.

 

 

 

 