10-1 Inspections

Daily or periodic inspections are required in order to maintain the FQM1 in peak operating condition.

10-1-1 Inspection Points

Although the major components in the FQM1 have an extremely long life time, they can deteriorate under improper environmental conditions. Periodic inspections are thus required to ensure that the required condition is being maintained.

Inspection is recommended at least once every six months to a year, but more frequent inspections will be necessary in adverse environments.

Take immediate steps to correct the situation if any of the conditions in the fol- lowing table are not met.

Inspection Points for Periodic Inspections

No.

Item

Inspection

Criteria

Action

 

 

 

 

 

1

Source Power

Check for voltage fluctuations

The voltage must be within

Use a voltage tester to check the

 

Supply

at the power supply terminals.

the allowable voltage fluctu-

power supply at the terminals. Take

 

 

 

ation range.

necessary steps to bring voltage

 

 

 

(See note.)

fluctuations within limits.

 

 

 

 

 

2

I/O Power Sup-

Check for voltage fluctuations

Voltages must be within

Use a voltage tester to check the

 

ply

at the I/O terminals.

specifications for each

power supply at the terminals. Take

 

 

 

Module.

necessary steps to bring voltage

 

 

 

 

fluctuations within limits.

 

 

 

 

 

3

Ambient environ-

Check the ambient tempera-

0 to 55°C

Use a thermometer to check the

 

ment

ture. (Inside the control panel

 

temperature and ensure that the

 

 

if the FQM1 is in a control

 

ambient temperature remains

 

 

panel.)

 

within the allowed range of 0 to

 

 

 

 

55°C.

 

 

 

 

 

 

 

Check the ambient humidity.

Relative humidity must be

Use a hygrometer to check the

 

 

(Inside the control panel if the

10% to 90% with no con-

humidity and ensure that the ambi-

 

 

FQM1 is in a control panel.)

densation.

ent humidity remains within the

 

 

 

 

allowed range.

 

 

 

 

In particular, verify that there is no

 

 

 

 

condensation or icing caused by

 

 

 

 

sudden temperature changes.

 

 

 

 

 

 

 

Check that the FQM1 is not in

Not in direct sunlight

Protect the FQM1 if necessary.

 

 

direct sunlight.

 

 

 

 

 

 

 

 

 

Check for accumulation of

No accumulation

Clean and protect the FQM1 if nec-

 

 

dirt, dust, salt, metal filings,

 

essary.

 

 

etc.

 

 

 

 

 

 

 

 

 

Check for water, oil, or chemi-

No spray on the FQM1

Clean and protect the FQM1 if nec-

 

 

cal sprays hitting the FQM1.

 

essary.

 

 

 

 

 

 

 

Check for corrosive or flam-

No corrosive or flammable

Check by smell or use a sensor.

 

 

mable gases in the area of the

gases

 

 

 

FQM1.

 

 

 

 

 

 

 

 

 

Check the level of vibration or

Vibration and shock must

Install cushioning or shock absorb-

 

 

shock.

be within specifications.

ing equipment if necessary.

 

 

 

 

 

 

 

Check for noise sources near

No significant noise

Either separate the FQM1 and

 

 

the FQM1

sources

noise source or protect the FQM1.

 

 

 

 

 

260

Page 283
Image 283
Omron FQM1-MMA21, FQM1-CM001, FQM1-MMP21 Inspection Points for Periodic Inspections, Inspection Criteria Action