Brocade Communications Systems 53-1002373-02 manual Cable management notes

Models: 53-1002373-02

1 452
Download 452 pages 21.42 Kb
Page 153
Image 153

Installing a Brocade MLXe-32 router

2

FIGURE 99 Accessing modules by shifting cable bundles

1

1 Cable bundles

Cable management notes

The following rules apply when setting up cable management for a heavily- or fully-loaded system:

All cables must be firmly connected, supported, and contained.

Use cable cinches, spaced approximately every 24 inches, to secure all of the cables for each module into a single bundle. This is especially important at the ends nearest the module connections. Each cable cinch holds up to 8 MRJ21 cables, or 48 RJ45 cables.

For additional security, use cable ties to secure cables to the cable management system hardware on the sides of the unit.

The cable routing slots at the top and bottom of the unit are strong enough to hold many cables, but the more cable cinches and cable ties you use, the more secure your cable management system will be.

If you bundle the cables correctly, you will be able to move the bundles to the side to access the modules for service, without disturbing the connections. Refer to Figure 99.

Always route the cables for the outer-most modules out the sides of the unit. Route the cables for the innermost modules through the top or through the bottom cable management hardware on the unit.

Brocade MLX Series and Brocade NetIron XMR Hardware Installation Guide

135

53-1002373-02

 

Page 153