4 Installing a Brocade NetIron XMR 32000 router

FIGURE 208 Removing the power lugs (2400W power supply and 3000W power supply displayed)

1

2

2

1 Lug screws

2

Power lug (2)

3.Crimp the correct AWG wire into the power lugs: For 2400 W power supply, crimp #4 AWG

For 3000 W power supply, crimp #2 AWG. Refer to Figure 209.

CAUTION

1

For the NEBS-compliant installation of a Brocade NetIron XMR 4000, 8000, and 16000 routers with AC and DC systems, use a ground wire of at least 6 American Wire Gauge (AWG). The ground wire should have an agency-approved crimped connector (provided with the router) attached to one end, with the other end attached to building ground. The connector must be crimped with the proper tool, allowing it to be connected to both ground screws on the enclosure. Before crimping the ground wire into the provided ground lug, insure the bare copper wire has been cleaned and antioxidant is applied to the bare wire.

294

Brocade MLX Series and NetIron XMR Hardware Installation Guide

 

53-1002373-02