7 Managing the cooling system

For the <low-threshold> and <high-threshold> parameters, you can specify any temperature in Centigrade. However, when changing low and high temperature thresholds for module fan speeds, remember that the low temperature threshold of a higher fan speed must be lower than the high temperature threshold of the lower fan speed. Brocade has established this guideline to ensure fan speed stability.

For example, if you are changing the temperature thresholds for a management module high and medium-high fan speeds, the system will accept the following values because the low temperature threshold for the high speed (79° C) is lower than the high temperature threshold (82 ° C) for the medium-high speed.

Fan speed

Low temperature threshold

High temperature threshold

 

 

 

High

79° C

87° C

 

 

 

Medium-high

69° C

82° C

 

 

 

The device will not accept the following values because the low temperature threshold for the high speed (83° C) is higher than the high temperature threshold (82° C) for the medium-high speed.

Fan speed

Low temperature threshold

High temperature threshold

 

 

 

High

83° C

87° C

 

 

 

Medium-high

69° C

82° C

 

 

 

Displaying temperature thresholds for modules and fan speeds

To check the current settings of the low and high temperature thresholds for modules and fan speeds, you can enter the show fan-thresholdcommand at any level of the CLI.

Brocade# show fan-threshold

=== Thermal Sensor

Control Block (THERMAL_SENSOR_TEST_RULE_MP) ===

Fan Speed

Low: -1

- 60

 

Fan Speed

Med: 57

- 70

80

Fan Speed

Med-Hi:

67 -

Fan Speed

Hi: 77 -

85

 

state = 0

(FAN_STATE_LOW)

max_ts_shut_off_count = 1

shut_off_count = 0

0 0

0 0 0 0 0 0 0 0 0 0 0 0 0

=== Thermal Sensor

Control Block (THERMAL_SENSOR_TEST_RULE_SNM) ===

Fan Speed

Low: -1

- 30

 

Fan Speed

Med: 27

- 40

50

Fan Speed

Med-Hi:

37 -

Fan Speed

Hi: 47 -

75

 

state = 2

(FAN_STATE_MED_HI)

max_ts_shut_off_count = 1

shut_off_count = 0

0 0

0 0 0 0 0 0 0 0 0 0 0 0 0

=== Thermal Sensor

Control Block (THERMAL_SENSOR_TEST_RULE_LP) ===

Fan Speed

Low: -1

- 50

 

Fan Speed

Med: 46

- 55

60

Fan Speed

Med-Hi:

51 -

Fan Speed

Hi: 56 -

95

 

state = 0

(FAN_STATE_LOW)

max_ts_shut_off_count = 1

shut_off_count = 0

0 0

0 0 0 0 0 0 0 0 0 0 0 0 0

=== Thermal Sensor

Control Block (THERMAL_SENSOR_TEST_RULE_LP_XPP) ===

Fan Speed

Low: -1

- 50

 

Fan Speed

Med: 45

- 65

75

Fan Speed

Med-Hi:

60 -

334

Brocade MLX Series and Brocade NetIron XMR Hardware Installation Guide

 

53-1002373-02

Page 352
Image 352
Brocade Communications Systems 53-1002373-02 manual Displaying temperature thresholds for modules and fan speeds