3 Installing a Brocade MLX-32 router
CAUTION
For the
CAUTION
For the
CAUTION
To ensure adequate bonding when attaching the ground lug, a minimum of 20 PSI of torque is required to be applied to the mounting hardware used to attach the ground lug.
FIGURE 163 Crimping the power supply wire in the lug
12
1#4 AWG for 2400W power supply #2 AWG for 3000W power supply.
2
1
2 Power lug
4.Reconnect the power lugs to the power supply unit.
5.Connect the
NOTE
DC return must be isolated from the router ground
6.Replace the safety cover. Refer to Figure 163.
This equipment installation must meet NEC/CEC code requirements. Consult local authorities for regulations.
226 | Brocade MLX Series and Brocade NetIron XMR Hardware Installation |