Brocade Communications Systems 53-1002373-02 manual Cover screws and DC power lugs

Models: 53-1002373-02

1 452
Download 452 pages 21.42 Kb
Page 207
Image 207

Installing a Brocade MLX-16 router

3

Follow these steps to connect a DC power source.

1.Use a #1 Phillips screwdriver to remove the two screws that hold the transparent cover over the power supply lugs, as shown in Figure 133.

FIGURE 133 Cover screws and DC power lugs

2

IN DC OUT

1

1 Transparent cover screws

2 Power lugs

2.Use a #2 Phillips head screwdriver to remove the power lugs.

3.Crimp #8 AWG power supply wire into the power lugs and reconnect the power lugs to the power supply unit. Refer to Figure 134.

CAUTION

For the NEBS-compliant installation of a Brocade router with AC and DC systems, use a ground wire of at least 6 American Wire Gauge (AWG). The ground wire should have an agency-approved crimped connector (provided with the device) attached to one end, with the other end attached to building ground. The connector must be crimped with the proper tool, allowing it to be connected to both ground screws on the enclosure. Before crimping the ground wire into the provided ground lug, ensure the bare copper wire has been cleaned and antioxidant is applied to the bare wire.

CAUTION

To ensure adequate bonding when attaching the ground lug, a minimum of 20 PSI of torque is required to be applied to the mounting hardware used to attach the ground lug.

FIGURE 134 Crimping the power supply wire in the power lug

1

Brocade MLX Series and Brocade NetIron XMR Hardware Installation Guide

189

53-1002373-02

 

Page 207
Image 207
Brocade Communications Systems 53-1002373-02 manual Cover screws and DC power lugs