192Chapter 9: Meridian Link/CCR interface cabling

NT8D11 backplane cable reroutingÑto accommodate the IPE Module in PE slots 0Ð3

With the cables located as shown in Table 64, use the following procedure to reroute the backplane cables. Note that an IPE Module located in slots 0Ð3 uses I/O connector ports A and D.

1Leave cable A in slot position L0.

2Remove cable C from the backplane and connect cable ends C-1, C-2, and C-3 to slot positions L3-1, L3-2, and L3-3.

3Move the C connector on the I/O panel to position D. Now the cable designation is changed from C to D.

!

CAUTION

Risk of hardware damage

With this cable rerouting, the IPE Module can be used only in PE slots 0Ð3. Also, when the IPE Module is not in PE slots 0Ð3, PE slot 2 should not be used at all.