1152700 • Issue 1 • February 2001 • Section 2 Operation and Maintenance
Page 1 of 2
SET SHELF HOUSEKEEPING ALARM CONFIGURATION
Summary: This procedure details the steps required to configure the housekeeping alarm messages that will be displayed when an input is triggered via an external source.
1.From the shelf level GUI Chassis View window, select the Fault pull down menu using the mouse to click on it, or by entering “Alt+A” on the keyboard. Refer to Figure
2.Select the Configure Housekeeping Alarms option using the down arrow keys to highlight it and hitting “Enter” or “Return”, or by entering an “Alt+A” on the keyboard.
3.The Housekeeping Alarms shelf level GUI display appears as shown in Figure
4.Enter in an alarm description for each of the eight alarm interfaces according to the type of equipment hardwired to the SC EIM card. Refer to the label located inside the front door panel if necessary. This label should have been filled out by the installer during installation. Refer to List of related Publications in the preface of this manual for installation procedures.
5.Select the Apply button at the bottom of the window to send the new configuration data to the database.
6.Select the Close button at the bottom of the window to return to the shelf level GUI Chassis View screen.
Stop! You have completed this procedure.
SELECT THE FAULT PULLDOWN MENU USING LEFT MOUSE BUTTON OR BY PRESSING THE ALT+A KEYS SIMULTANEOUSLY.
| Cellworx Vision: Chassis View, Network Element 2 |
|
| X |
|
|
|
|
|
|
|
File | Configuration | Fault |
| Security |
|
|
|
|
|
|
|
|
| Configure Housekeeping Alarms |
|
|
| ||||||
S | N | Execute Alarm | RE RRE | 6 | 6 | S | |||||
T | T | T | T | T | |||||||
C | M | 3 M | 1 | 3 | 3 1 1 | 2 | 2 | C | |||
| I | T | U | M |
|
| M | M | 2 | 2 |
|
| C | M | X | u | C | C | u | u |
|
|
|
|
| U |
| l | R | R | l | l | R | R |
|
|
| X | E | t | S | S | t | t | i | i |
|
|
|
| X | i |
|
| i | i | n | n |
|
Figure 750-1. Shelf Level GUI Fault Pull Down Menu