1152700 Issue 1 February 2001 Section 2 Operation and Maintenance

DLP-761

Page 3 of 3

Table 761-1. Display T3 Card Status Definitions, continued

ITEM

Line Status

STATUS

No Alarm

Rcv RAI

Failure

Xmt RAI

Alarm

Rcv AIS

Xmit AIS

LOF

LOS

Loopback

State

Rcv Test Code

Other Failure

DEFINITION

T3 line is operating within normal parameters.

Access interface (AIC) Receiving Remote Alarm Indication.

Card transmitting a Remote Alarm Indication signal (RAI) to customer equipment.

Card is receiving an Alarm Indication Signal (AIS).

Card is transmitting an AIS signal.

Input signal frame format not recognized.

No input signal being received.

Card has been manually set to loop signal back to customer equipment.

Card is receiving a test signal input.

Card is experiencing a failure other than these listed.

ACTION

No action required.

Check VP connection per DLP-710, and local access interface.

Check VP connection per DLP-710, and remote transmit end.

Check remote end T3 input signal.

Check local T3 signal input.

Verify correct frame format setting and change if needed per DLP-753.

Check metallic input and DSX.

Check customer end for troubleshooting activity. If required, release loopback per DLP-772.

Check with administrator for testing activity.

Page 2-274

© 2000, ADC Telecommunications, Inc.

Page 294
Image 294
ADC Release 3.1 user manual Display T3 Card Status Definitions, Lof Los