TURN UP (PROVISION) CELLWORX STN EXPANSION SHELVES
Summary: This procedure describes the steps required to add a Cellworx STN expansion shelf
Note: Applications using the
Prerequisites to this procedure are:
•Ring node must be
•Shelf ExPansion Interface Cards (SEPICs) cards must be installed and
•Shelf ExPansion Interface Cards (SEPICs) must be installed in the expansion shelf.
•Expansion shelf must have shelf type set to 03 for expansion NE. This is accomplished by the thumbwheel switch on SC TEIM in slot 18 at the rear of the shelf and should have been set during shelf installation procedures. If shelf type is changed, SC card must be reset using the button under the front hinged faceplate. Refer to the Installation Manual 1152693.
1. | Ensure there is not a Level 1 GUI user logged onto the system. |
|
| If necessary, force the user session off using the following |
|
| procedure: | |
2. | Launch the Cellworx Vision GUI from the |
3.Double click on the icon representing the ring node that will have the expansion shelf
4.Verify that the expansion shelf interfaces in the ring node are equipped and
5.If the expansion shelf interface cards are not installed, refer to
the Cellworx STN Installation Manual for card installation |
|
procedures. | 1152693 |
6.Verify the cards are configured as Shelf Expansion Interfaces for either of the following:
155 SM/MM CRS cards | |
622 SM CRS cards | |
T3 CRS cards |