4.HOW TO MONITOR REDUNTANT SYSTEM

This section explains the restrictions on the connection methods and other information applicable when the QCPU redundant system is monitored by the GOT.

Monitor target

module

supplyPower

Q25PRHCPU

Control

system

(System A)

Tracking cable

 

Station No. 0

 

 

 

 

 

Station No. 1

 

 

-QJ71LP21

(Multiplexed remote master station)

Q25PRHCPU

25-QJ71LP21

(Multiplexed remote sub master station)

QJ71BR11

100-QJ71E71

QJ61BT11N

Empty

supplyPower module

QJ71BR11

100-QJ71E71

QJ61BT11N

Empty

Standby

system

(System B)

remote I/O network

Station No. 2 (remote I/O station)

supply Power module

25-

Empty

Empty

 

 

 

 

 

 

 

The GOT monitors

 

 

 

 

 

 

 

 

 

 

 

 

 

CPU direct

 

 

GOT

 

the control system

 

 

 

 

 

PLC CPU.

 

connection

 

 

 

 

 

 

 

 

 

 

 

When an error occurs in System A, System B switches from standby system to control system.

module

supplyPower

Q25PRHCPU

Standby

system

(System A)

Tracking cable

 

 

 

 

 

 

Monitor target

 

 

 

 

Station No. 0

 

 

 

 

 

Station No. 1

 

 

 

(Multiplexed remote master station)

Q25PRHCPU

25-QJ71LP21

(Multiplexed remote sub master station)

-

-

QJ61BT11N

Empty

supplyPower module

QJ71BR11

100-QJ71E71

QJ61BT11N

Empty

Control

system

(System B)

MELSECNET/H remote I/O network

Station No. 2 (remote I/O station)

supply Power module

25-QJ72LP25

QJ71C24N

Empty

Empty

The GOT monitors the PLC CPU

GOT of the new control system after

CPU direct system switching. connection

In a redundant system, the monitoring can be performed with the monitoring target specified as the control system or the standby system on the GOT. By specifying the monitoring target PLC CPU as the control system of the redundant system, the monitoring target is automatically changed to the PLC CPU in the control system when system switching occurs.

To enable this automatic changing of the monitoring target at the GOT, settings are required in the GT Designer3. 4.9 Q Redundant Setting

4 - 2

4. HOW TO MONITOR REDUNTANT SYSTEM