(2)CC IE Control Utility's [Parameter Settings]

(a)Parameter settings

 

 

 

 

Setting

 

Item

 

Set value

necessity at

 

 

GOT

 

 

 

 

 

 

 

 

connection

Number of modules

 

1

 

 

 

 

 

Link device refresh cycle

 

(Use default value)

 

 

 

 

 

Routing parameter

 

Refer to (c)

 

 

 

 

 

Target module

 

1

 

 

 

 

 

Start I/O No.

 

0000H

 

 

 

 

 

Channel No.

 

151

 

 

 

 

 

 

 

Network type

 

CC IE Control

 

settings

 

(Control station)

 

 

 

 

 

 

 

 

Mode*1

 

Online

 

 

 

 

Operation

Network No.*2

 

1

 

 

 

 

 

Group No.

 

0

 

 

 

 

 

 

 

Station No.

 

1

 

 

 

 

 

 

Refresh parameters

 

(Use default value)

 

 

 

 

 

Network range

 

Refer to (b)

 

assignment

 

 

 

 

 

 

 

 

 

 

 

 

: Necessary : As necessary : Not necessary

*1 Set the same mode setting as that of the GOT.

*2 Specify the same network No. as that of the GOT.

(b) Network range assignment

 

 

 

 

 

 

Setting

 

Item

 

Set value

necessity at

 

 

GOT

 

 

 

 

 

 

 

 

 

 

 

 

connection

Total stations

 

2

 

 

 

 

 

 

 

 

 

 

Station

 

Start

0000H

 

 

LB

No.1

 

End

00FFH

 

 

 

 

 

 

 

 

 

 

 

 

Station

 

Start

0100H

 

 

 

 

 

LB/LW

 

No.2

 

End

01FFH

 

 

 

 

 

 

 

 

 

 

 

settings (1)

 

Station

 

Start

00000H

 

 

 

 

 

 

LW

No.1

 

End

000FFH

 

 

 

 

 

 

 

 

 

 

 

 

Station

 

Start

00100H

 

 

 

 

 

 

 

No.2

 

End

001FFH

 

 

 

 

 

 

 

 

 

 

 

 

 

LX/LY settings*1

 

No setting

 

Monitoring time

 

(Use default value)

 

 

 

 

 

Specify I/O master station*1

 

No setting

 

Specify reserved station

 

No setting

 

 

 

 

 

Supplementary settings

 

(Use default value)

 

 

 

 

 

 

 

 

: Necessary : As necessary : Not necessary *1 Be sure to set it to perform the cyclic transmission.

POINT

When changing the network parameter

After writing the network parameter to the C Controller module, either turn the C Controller module OFF and then ON or reset it.

9

MELSECNET/H(PLCNETWORK) CONNECTIONPLC TO 10

MELSECNET/10(PLCNETWORK) CONNECTIONPLC TO 11

CONTROLLERIE NETWORK CONNECTION Link-CC 12

FIELDIE NETWORK CONNECTION Link-CC 13

CONNECTIONLink DEVICE(INTELLIGENT STATION) -CC 14

Link CONNECTION G4) -CC (Via 15

INVERTER CONNECTION 16

SERVO AMPLIFIERCONNECTION

11. CC-Link IE CONTROLLER NETWORK CONNECTION

11 - 13

11.4 PLC Side Setting