Precautions when preparing a cable

(1)Cable

Use a shielded twisted pair cable of 0.3mm2 or more as a cable for GOT multi-drop connection.The following shows recommended model names and manufacturers of the cable to be used.

Manufacturer

Model

 

 

 

Remark

Mitsubishi Cable

SPEV(SB)-0.5-2P

Two-pair cable of

Industries,Ltd

0.5mm2

 

 

 

Showa Electric Wire &

KMPEV-SB

 

 

Two-pair cable of

Cable Co.,Ltd

CWS-178 0.5SQ

2P

0.5mm2

 

DPEV SB 0.3

 

3P

Three-pair cable of

Sumitomo Electric

 

0.3mm2

 

 

 

Industries.,Ltd

DPEV SB 0.5

 

3P

Three-pair cable of

 

 

0.5mm2

 

 

 

 

The Furukawa Electric

D-KPEV-SB 0.5

3P

Three-pair cable of

Co.,Ltd

0.5mm2

 

 

 

 

IPEV-SB 2P

0.3 mm2

Two-pair cable of

 

0.3mm2

Fujikura Ltd.

 

 

 

IPEV-SB 2P

0.5 mm2

Two-pair cable of

 

 

0.5mm2

 

 

 

 

 

 

 

 

 

 

 

Pair

Shield

(3)GOT side connector

For the GOT side connector, refer to the following.

1.4.1 GOT connector specifications

Connecting terminating resistors

When connecting a Serial Multi-Drop Connection Unit to the GOT, a terminating resistor must be connected to the GOT.

(a)For GT16, GT15, GT12

Set the terminating resistor setting switch.

(b)For GT14, GT11, GT10

Set the terminating resistor selector switch.

For the procedure to set the terminating resistor, refer to the following.

1.4.3 Terminating resistors of GOT

Two-pair cable structural

drawing exampleThree-pair cable structural drawing example

(2)Cable for converting D-sub9 pin connector to terminal block

Create by yourself, referring to the following connection diagram.

Example of connection diagram for 2 pair wiring

SDA1

 

 

 

 

1

SDA

 

 

 

 

SDB1

 

 

 

 

6

SDB

 

 

 

 

RDA1

 

 

 

 

2

RDA

 

 

 

 

RDB1

 

 

 

 

7

RDB

 

 

 

 

SDA2

 

 

 

 

5

SG

 

 

 

 

SDB2

 

 

 

 

3

RSA

RDA2

 

 

 

 

8

RSB

RDB2

 

 

 

 

4

CSA

 

 

 

 

SG

 

 

 

 

9

CSB

 

 

 

 

FG

 

 

 

 

Shell

FG

Make sure to connect the wiring branched on the GOT side connector.

Use a shielded twisted pair cable of 0.2mm2 or more. Use an applicable cable to D-sub connector.

Wiring should be the shortest distance.

19 - 22

19. GOT MULTI-DROP CONNECTION

 

19.4 Connection Diagram