15.5.2Connecting FREQROL-E500 series

Communication settings

Make the communication settings of the inverter.

Be sure to perform the inverter reset after updating each parameter.

(1) Communication port and corresponding parameters

GOT connection

Parameters corresponding to inverter

destination

 

PU connector

Pr.79, Pr.117 to Pr.124, Pr.146, Pr.342

 

 

(2)Communication settings of inverter

Set the following parameters using the PU (parameter unit).

Do not change these parameters, even though they can be monitored from the GOT.If they are changed, communication with the GOT is disabled.

Setting item*1

Parameter No.

Set value

 

Contents of setting

Communication station number

Pr.117

0 to 31

 

15.5.12 Station number

 

 

setting

 

 

 

 

 

 

 

 

 

Communication speed*2

Pr.118

192*3

 

19200bps

Stop bit length*2

Pr.119

10

 

Data length: 7bit

 

Stop bit length: 1bit

 

 

 

 

 

 

 

 

 

Parity check presence/absence*2

Pr.120

1

 

Odd

Number of communication retries

Pr.121

9999

The inverter will not come to an

(65535)

 

alarm stop.

 

 

 

 

 

 

 

 

Communication check time interval

Pr.122

9999

 

Communication check

 

suspension

 

 

 

 

 

 

 

 

 

Wait time setting

Pr.123

0

 

0ms

 

 

 

 

 

CRLF presence/ absence selection

Pr.124

1*3

 

With CR, without LF

Protocol selection*4

 

Operation mode selection

Pr.79

1*3

 

PU operation mode

Communication startup mode selection*4

 

E2PROM write selection

Pr.342

0*3

 

Written to RAM and EEPROM

Frequency setting command selection*5

Pr.146

9999

 

Built-in frequency setting

 

potentiometer invalid

 

 

 

 

 

 

 

 

 

*1 Setting items are parameter names described in the manual of FREQROL-E500 series.

*2 Settings on the GOT can be changed.

When changing the settings on the GOT, be sure to change the parameters on the inverter to correspond with the GOT settings.

*3 Inverter default values (No need to change)

*4 There is no Protocol selection setting on the inverter side.

*5 The setting is required for Frequency setting command selection.

15 - 32

15. INVERTER CONNECTION

 

15.5 FREQROL Series Inverter Side Settings