Ethernet Adapter Module setting
Set the parameter with the Ethernet adapter module setting tool.
For details of the setting method, refer to the following manual.
(1)
Item | Set value |
Network No. | 1*1 |
Station No. | 1*2 |
*1 Set the same value as the network No. set on the PLC side. *2 Set a value other than the network No. set on the PLC side.
(2) Ethernet setting
Item | Set value |
IP address | 192.168.3.30*1 |
*1 Set the IP address within the following range.
192.168. 3. 30
Set the fourth octet within the range from 1 to 64.
Set the third octet within the range from 1 to 239.
[Controller Setting] and [Ethernet] of GT Designer3
POINT
[Controller Setting] and [Ethernet] of GT Designer3
For [Controller Setting] and [Ethernet] of GT Designer3, refer to the following.
8.3.1 Setting communication interface (Communication settings)
(1) Controller setting
Item | Set value (Use default value) | |
GOT NET No. | 3*1 | |
GOT PC No. | 1 | |
|
| |
GOT IP Address | 192.168.3.18 | |
|
| |
GOT Port No. (Communication) | 5001 | |
|
| |
GOT Port No. | 5014 | |
(Ethernet Download) | ||
| ||
|
| |
Default Gateway | 0.0.0.0 | |
|
| |
Subnet Mask | 255.255.255.0 | |
|
| |
Retry | 3 times | |
|
| |
Startup Time | 3 sec | |
|
| |
Timeout Time | 3 sec | |
|
| |
Delay Time | 0ms | |
|
|
*1 Set the GOT network No. according to the third octet (network No.) of the Ethernet adapter module IP address.
(2) Ethernet setting
| Item | Set value | |
|
| Host | * |
|
|
|
|
|
| N/W No. | 3*1 |
Ethernet Setting |
| PC No. | 30*2 |
| Type | ||
No.1 |
| ||
|
|
| |
|
| IP address | 192.168.3.30*3 |
|
| Port No. | 5001(fixed) |
|
|
|
|
|
| Communication | UDP(fixed) |
|
|
|
|
*1 Set according to the third octet (network No.) of the Ethernet adapter module IP address.
*2 Set according to the fourth octet (PC No.) of the Ethernet adapter module IP address.
*3 Set according to the Ethernet adapter module IP address.
(3) Routing parameter setting
Item | Set value |
Transfer Network No. | 1*1 |
Relay Network No. | 3*2 |
Relay Station No. | 30*3 |
*1 Set the same value as the Ethernet adapter module network No.
*2 Set according to the third octet (network No.) of the Ethernet adapter module IP address.
*3 Set according to the fourth octet (PC No.) of the Ethernet adapter module IP address.
1
PREPARATORYFORPROCEDURESMONITORING 2
RANGESETBE
DEVICE CANTHAT 3
RANGEACCESS MONITORINGFOR 4
MONITORTOREDUNTANTSYSTEM HOW 5
CONNECTIONBUS 6
DIRECTTOCONNECTIONCPU 7
LINKCOMPUTER CONNECTION 8
ETHERNETCONNECTION
8. ETHERNET CONNECTION | 8 - 45 |
8.4 PLC Side Setting |
|