Ethernet Adapter Module setting

Set the parameter with the Ethernet adapter module setting tool.

For details of the setting method, refer to the following manual.

CC-Link IE Field Network Ethernet Adapter Module User's Manual

(1) CC-Link IE Field Network setting

Item

Set value

Network No.

1*1

Station No.

1*2

*1 Set the same value as the network No. set on the PLC side. *2 Set a value other than the network No. set on the PLC side.

(2) Ethernet setting

Item

Set value

IP address

192.168.3.30*1

*1 Set the IP address within the following range.

192.168. 3. 30

Set the fourth octet within the range from 1 to 64.

Set the third octet within the range from 1 to 239.

[Controller Setting] and [Ethernet] of GT Designer3

POINT

[Controller Setting] and [Ethernet] of GT Designer3

For [Controller Setting] and [Ethernet] of GT Designer3, refer to the following.

8.3.1 Setting communication interface (Communication settings)

(1) Controller setting

Item

Set value (Use default value)

GOT NET No.

3*1

GOT PC No.

1

 

 

GOT IP Address

192.168.3.18

 

 

GOT Port No. (Communication)

5001

 

 

GOT Port No.

5014

(Ethernet Download)

 

 

 

Default Gateway

0.0.0.0

 

 

Subnet Mask

255.255.255.0

 

 

Retry

3 times

 

 

Startup Time

3 sec

 

 

Timeout Time

3 sec

 

 

Delay Time

0ms

 

 

*1 Set the GOT network No. according to the third octet (network No.) of the Ethernet adapter module IP address.

(2) Ethernet setting

 

Item

Set value

 

 

Host

*

 

 

 

 

 

 

N/W No.

3*1

Ethernet Setting

 

PC No.

30*2

 

Type

NZ2GF-ETB

No.1

 

 

 

 

 

 

IP address

192.168.3.30*3

 

 

Port No.

5001(fixed)

 

 

 

 

 

 

Communication

UDP(fixed)

 

 

 

 

*1 Set according to the third octet (network No.) of the Ethernet adapter module IP address.

*2 Set according to the fourth octet (PC No.) of the Ethernet adapter module IP address.

*3 Set according to the Ethernet adapter module IP address.

(3) Routing parameter setting

Item

Set value

Transfer Network No.

1*1

Relay Network No.

3*2

Relay Station No.

30*3

*1 Set the same value as the Ethernet adapter module network No.

*2 Set according to the third octet (network No.) of the Ethernet adapter module IP address.

*3 Set according to the fourth octet (PC No.) of the Ethernet adapter module IP address.

1

PREPARATORYFORPROCEDURESMONITORING 2

RANGESETBE

DEVICE CANTHAT 3

RANGEACCESS MONITORINGFOR 4

MONITORTOREDUNTANTSYSTEM HOW 5

CONNECTIONBUS 6

DIRECTTOCONNECTIONCPU 7

LINKCOMPUTER CONNECTION 8

ETHERNETCONNECTION

8. ETHERNET CONNECTION

8 - 45

8.4 PLC Side Setting