2.2 MELSEC-L
The device ranges that can be set when selecting
| Device name |
| Setting range | Device No. | |||
|
| representation | |||||
|
|
|
|
|
| ||
| Input (X) |
| X0 | to | X3FFF | Hexadecimal | |
|
|
|
|
|
| ||
| Output (Y) |
| Y0 | to | Y3FFF | ||
|
|
| |||||
|
|
|
|
|
| ||
| Internal relay (M)*4*6 | M0 | to | M61439 |
| ||
| Latch relay (L) | L0 | to | L32767 | Decimal | ||
|
|
|
|
|
| ||
| Annunciator (F) | F0 | to | F32767 |
| ||
|
|
|
|
|
| ||
| Link relay (B)*4 | B0 | to | BEFFF | Hexadecimal | ||
| Timer*6 | Contact (TT) | TT0 | to | TT32767 |
| |
|
|
|
|
|
| ||
| Coil (TC) | TC0 | to | TC32767 |
| ||
|
|
| |||||
|
|
|
|
|
|
| |
device | Counter*6 | Contact (CT) | CT0 | to | CT32767 |
| |
|
|
|
|
| |||
Coil (CC) | CC0 | to | CC32767 | Decimal | |||
| |||||||
|
|
|
|
| |||
Special relay (SM) | SM0 | to | SM2047 | ||||
Bit |
| ||||||
|
|
|
|
|
| ||
| Retentive | Contact (SS) | SS0 | to | SS32767 |
| |
| timer*6 |
|
|
|
|
| |
| Coil (SC) | SC0 | to | SC32767 |
| ||
| Step relay (S) | S0 | to | S8191 |
| ||
|
|
|
|
|
| ||
| Link special relay (SB) | SB0 | to | SB7FFF | Hexadecimal | ||
|
|
|
|
| |||
|
|
| Specified bit of the |
| |||
|
|
| following word devices |
| |||
| Word device bit | (Except Timer, Counter, | ― | ||||
| Retentive timer, Index | ||||||
|
|
|
| ||||
|
|
| register and Buffer |
| |||
|
|
|
| memory) |
| ||
|
|
|
|
|
| ||
| Data register (D)*4*6 | D0 | to | D421887 | Decimal | ||
| Special data register (SD) | SD0 | to | SD2047 | |||
|
| ||||||
|
|
|
|
|
| ||
| Link register (W)*4 | W0 | to | W66FFF | Hexadecimal | ||
| Timer (current value) (TN)*6 | TN0 | to | TN32767 |
| ||
| Counter (current value) | CN0 | to | CN32767 |
| ||
| (CN)*6 |
| Decimal | ||||
|
|
|
|
| |||
| Retentive timer | SN0 | to | SN32767 |
| ||
| (current value) (SN)*6 |
| |||||
|
|
|
|
| |||
| Link special register (SW) | SW0 | to | SW7FFF | Hexadecimal | ||
|
|
|
|
|
| ||
| File register (R)*1*2 | R0 | to | R32767 |
| ||
device | Extension file register | ZR0 | to | ZR393215 |
| ||
(ZR)*1*3*4 |
|
| |||||
|
|
|
|
| |||
Word | Index register (Z) | Z0 | to | Z19 |
| ||
|
|
|
|
|
| ||
Buffer memory |
|
|
| Decimal | |||
|
|
|
| ||||
| (Intelligent function module) | BM0 | to | BM32767 | |||
|
| ||||||
| (BM)*5 |
|
|
|
|
| |
| Buffer memory |
|
|
|
| ||
| (Intelligent function module) | G0 | to | G65535 |
| ||
| (G)*4*5 |
|
|
|
|
| |
| Ww*7*8 |
| Ww0 | to | Ww1FFF | Hexadecimal | |
| Wr*7*8 |
| Wr0 | to | Wr1FFF | ||
|
|
| |||||
|
|
| Converting the above bit |
| |||
| Bit device word*7*9 | devices into words | ― | ||||
| (Except Timer contact | ||||||
|
|
|
| ||||
|
|
| and Counter contact) |
| |||
|
|
|
|
|
|
|
*1 Do not set a file register by GT Designer3 when executing multiple programs with the file of the file register set at [Use the same file name as the program] by the PLC parameter of GX Developer.
Otherwise, read/write at GOT will be erroneous.
*2 Available for file register of block No. switched with the RSET instruction.
*3 Available for file register of block No. of file name switched with the QDRSET instruction.
*4 GOT treats them in units of 32k (32768 points).
*5 Only the intelligent function module on the station connected to GOT can be specified.
Set within the address range of the buffer memory existing in the target intelligent function module.
*6 Do not use local devices set in the
*7 This is not supported by GT10.
*8 This cannot be monitored when in GOT
*9 The device No. must be set in multiples of 16.
1
PREPARATORYFORPROCEDURESMONITORING 2
RANGESETBE
DEVICE CANTHAT 3
RANGEACCESS MONITORINGFOR 4
MONITORTOREDUNTANTSYSTEM HOW 5
CONNECTIONBUS 6
DIRECTTOCONNECTIONCPU 7
LINKCOMPUTER CONNECTION 8
ETHERNETCONNECTION
2. DEVICE RANGE THAT CAN BE SET | 2 - 9 |
2.2 |
|