Switch setting of CC-Link module (Q Series)

Set the station number setting switch, transmission speed / mode setting switch.

QJ61BT11N

QJ61BT11N

RUN

L RUN

MST

S MST

SD

RD

ERR.

L ERR.

STATION

NO.

X10

5

0

 

 

 

 

 

 

 

 

 

 

 

 

 

(1)

X1

5

0

 

 

 

 

 

 

 

 

 

 

Parameter setting (when connecting to MELSEC-Q or QS series)

(1)[Network parameter] of GX Developer

(a)Network parameter

9

TO CONNECTIONPLC MELSECNET/H(PLCNETWORK)

10

MELSECNET/10 CONNECTION (PLC TO PLC NETWORK)

MODE

NC

NC

DA

SLD

DB

(FG)

DG

C

8

0

 

4

1

2

3

4

5

6

7

(2)

11

CC-Link IE CONTROLLER NETWORK CONNECTION

12

(1) Station number setting switch

Station number

Description

Set value

Setting necessity

setting switch

at GOT connection

 

 

 

 

 

 

Station number

setting0 (fixed) (master station)

 

: Necessary

: As necessary : Not necessary

(2) Transmission rate/mode setting switch

 

 

 

 

Transmission

 

 

Setting necessity

rate/mode setting

Description

Set value

at GOT connection

switch

 

 

 

 

 

 

 

 

 

Transmission rate/mode

setting0 (Online:

156kbps)*1

: Necessary : As necessary : Not necessary *1 Specify the same transmission speed as that of the GOT.

POINT

When the switch setting has been changed

Turn the PLC CPU OFF then ON again, or reset the

PLC CPU.

 

 

Setting

Item

Set value

necessity at

GOT

 

 

 

 

connection

No. of boards in module

1

 

 

 

 

Start I/O No.*1

0000H

 

Operation setting

(Use default value)

 

 

 

 

Type

Master station

 

 

 

 

Mode

Remote net

 

(Ver.2 mode)

 

 

 

 

 

 

All connect count

1

 

 

 

 

Remote input (RX)

X400

 

 

 

 

Remote output (RY)

Y400

 

 

 

 

Remote register (RWr)

D300

 

 

 

 

Remote register (RWw)

D200

 

 

 

 

Special relay (SB)

SB0

 

 

 

 

Special register (SW)

SW0

 

 

 

 

Retry count

 

 

 

 

 

Automatic reconnection

 

 

station count

 

 

 

 

 

Stand by master station No.

(Use default value)

 

PLC down select

 

 

 

 

 

Scan mode setting

 

 

 

 

 

Delay information setting

 

 

 

 

 

Station information setting

Refer to (b)

 

 

 

 

Remote device station initial

 

 

setting

(Use default value)

 

Interrupt setting

 

 

 

 

 

: Necessary : As necessary : Not necessary

*1 When using Q170MCPU, set it according to the system configuration.

CC-Link IE FIELD NETWORK CONNECTION

13

CC-Link CONNECTION (INTELLIGENT DEVICE STATION)

14

CC-Link CONNECTION (Via G4)

15

CONNECTION

INVERTER

16

CONNECTION

SERVO AMPLIFIER

13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)

13 - 17

13.4 PLC Side Setting