[Network parameter] of GX Developer

(1) Network parameter

(2)Routing parameter setting

Up to 64 [Transfer Network No.]s can be set. However, the same transfer network number cannot be set twice or more (multiple times).

Therefore, the one that can access to other station from the request source host GOT is 64 kinds of [Transfer Network No.]s.

Item

 

Set value

Setting necessity

 

at GOT connection

 

 

 

Network type

 

Ethernet (fixed)

 

 

 

 

 

 

 

Start I/O No.

 

0000H

 

 

 

 

 

 

 

Network No.*1

 

1

 

 

Group No.

 

0 (fixed)

 

 

 

 

 

 

 

Station No.*2

 

2

 

 

IP address

 

192.168.0.19

 

 

 

 

 

 

 

Station No.<->IP

 

 

 

 

information

 

 

 

 

 

 

(Use default value)

 

 

FTP Parameters

 

 

 

 

 

 

 

 

 

 

 

 

Router relay parameter

 

 

 

 

 

 

 

 

 

Routing parameters

 

Refer to (2)

 

 

 

 

 

 

 

 

: Necessary : As necessary

: Not necessary

*1 Specify the same network No. as that of the GOT. *2 Do not set the same station No. as that of the GOT.

POINT

When changing the network parameter

After writing the network parameter to the PLC CPU, operate the PLC CPU ether turning OFF and then ON or resetting.

Item

Range

Target network No.

1 to 239

 

 

Relay network No.

1 to 239

 

 

Relay station No.

1 to 64

 

 

POINT

Routing parameter setting of request source

Routing parameter setting is also necessary for the request source GOT.

For the setting, refer to the following. 8.3.4 Routing parameter setting

8 - 32

8. ETHERNET CONNECTION

 

8.4 PLC Side Setting