[Controller Setting] of GT Designer3

(1)When MODEL GT15-J61BT13 CC-Link communication unit is used

Item

Set value

Station No.

1: Station No.1

 

 

Transmission Rate

0: Online 156kbps

 

 

Mode

Ver.1: Remote net (Ver.1 mode)

 

 

Expanded Cyclic

Single (Use default value)

 

 

Number of stations occupied

1 Station

 

 

Input for Error Station

0: Clear

 

 

Retry

3times (Use default value)

 

 

Timeout Time

3sec (Use default value)

 

 

Delay Time

0ms (Use default value)

 

 

(2)When MODEL GT15-75J61BT13-Z CC-Link communication unit is used

Item

Set value (Use default value)

Retry

3times

 

 

Timeout Time

3sec

 

 

POINT

[Controller Setting] of GT Designer3

For the setting method of [Controller Setting] of GT Designer3, refer to the following.

13.3.1 Setting communication interface (Communication settings)

Setting of the CC-Link communication unit (Only when MODEL GT15-75J61BT13-Z CC-Link communication unit is used)

 

Item

Set value

Mode setting switch

0: Online (fixed)

 

 

Station number setting switch

1: Station No.1

 

 

Transmission baudrate setting switch

0: 156kbps

 

 

 

Condition

SW1 (Input data status of the

OFF: Cleared

data link error station)

 

setting

 

 

SW2 (Number of occupied

 

switches

OFF: 1 station

 

stations)

 

 

 

 

 

POINT

Setting of the CC-Link communication unit

For the setting method of the CC-Link communication unit, refer to the following.

13.3.3 Switch setting (Only when MODEL GT15-75J61BT13-ZCC-Link communication unit is used)

13.4.2Connecting to CC-Link module (Q Series) with Ver.2 compatible

This section describes the settings of the GOT and CC- Link module (Q Series) in the following case of system configuration.

POINT

CC-Link module (Q Series)

For details of the CC-Link module (Q Series), refer to the following manual.

CC-Link System Master/Local Module User's Manual QJ61BT11N

System configuration

[Communication settings] of GT Designer3

<GOT>

(Use the default value for settings other than the following.)

Station type

: Intelligent device

 

station

Station No.

: Station No.1

Expanded cyclic setting : Single

Number of

: Exclusive station 1

stations occupied

 

Transmission speed

: 156kbps

<CC-Link module> *1

(Use the default value for the settings other than the following.)

Type

:

Master station

Station No.

:

Station No.0

Mode

:

Remote net (Ver.2 mode)

All connect count

:

1

Transmission speed :

156kbps

Switch setting of CC-Link module (Q Series)

[Network parameter] of GX Developer

*1 The CC-Link module is mounted on the base unit slot 0. The Start I/O No. of the CC-Link module is set to "0"

POINT

When connecting to Q170MCPU

When connected to Q170MCPU, the start I/O No. of the CC-Link module is set to "70".

13 - 16

13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)

 

13.4 PLC Side Setting