[Controller Setting] of GT Designer3
Item | Set value (Use default) |
Retry | 3times |
|
|
Timeout Time | 3sec |
|
|
POINT
[Controller Setting] of GT Designer3
For the setting method of [Controller Setting] of GT Designer3, refer to the following.
10.3.1 Setting communication interface (Communication settings)
Setting of the MELSECNET/10 communication unit
Item | Set value |
Network number setting switch | 1: Network No.1 |
|
|
Group number setting switch | 0: No group setting (fixed) |
|
|
Station number setting switch | 2: Station No.2 |
|
|
Mode setting switch | 0: Online (fixed) |
|
|
POINT
Setting of the MELSECNET/10 communication unit
For the setting method of the MELSECNET/10 communication unit, refer to the following.
10.3.1 Setting communication interface (Communication settings)
This section describes the settings of the GOT and MELSECNET/10 network module (A Series) in the following case of system configuration.
In this section, the network parameter (common parameter) of GX Developer is taken as an example to provide explanations.
POINT
MELSECNET/10 network module (A Series)
For details of the MELSECNET/10 network module (A Series), refer to the following manual.
Type MELSECNET/10 Network system (PLC to PLC network) Reference Manual
System configuration
■ [Controller Setting] of GT Designer3
■ Setting of the MELSECNET/10 communication unit
<GOT>
(Use the default value for settings other
than the following.) |
|
Station No. | : 2 |
Mode | : Online |
Network No. | : 1 |
MELSECNET/10 (PLC to PLC network) | Network range assignment: LB0100H to LB01FFH |
LW0100H to LW01FFH |
<MELSECNET/10 network module> *1
(Use the default value for settings other than the following.)
Station No. | : 1 |
Mode | : Online |
Network type | : MNET/10 (Control station) |
Network No. | : 1 |
Total stations | : 2 |
Network range assignment: LB0000H to LB00FFH
LW0000H to LW00FFH
■Switch setting of MELSECNET/10 network module
■[Network parameter] of GX Developer
*1 The MELSECNET/10 network module is mounted at slot 0 of the base unit.
The start I/O No. of the MELSECNET/10 network module is set at "0".
9
MELSECNET/H(PLCNETWORK) CONNECTIONPLC TO 10
MELSECNET/10 (PLC NETWORK) CONNECTION PLC TO 11
CONTROLLERIE NETWORK CONNECTION
FIELDIE NETWORK CONNECTION
CONNECTIONLink DEVICE(INTELLIGENT STATION)
Link CONNECTION G4)
INVERTER CONNECTION 16
SERVO AMPLIFIERCONNECTION
10. MELSECNET/10 CONNECTION (PLC TO PLC NETWORK) | 10 - 21 |
10.4 PLC Side Setting |
|