8.4.8Connecting to Display I/F (CNC C70)

This section describes the settings of the GOT and Display I/F (CNC C70) in the following case of the system configuration.

POINT

Display I/F (CNC C70)

For details of the Display I/F (CNC C70), refer to the following manual.

C70 Series SET UP MANUAL

System configuration

[Controller Setting] and [Ethernet] of GT

Designer3

<GOT> (The settings other than the following are set to the default)

Network No.

: 1

PLC No.

: 1

IP address

: 192.168.0.18

Port No.

: 5001

Communication format : UDP (fixed)

<Q17nNCCPU> (The settings other than the following are set to the default)

Network No.

: 239

PLC No.

: 2

IP address

: 192.168.0.19

Port No.

: 5001

Communication format

: UDP(fixed)

IP address settings of CNC C70

IP address settings of CNC C70

(1) Remote monitor tool

Item

Set value

Setting necessity at

GOT connection

 

 

IP address

192.168.0.19

 

 

 

 

Subnet mask

255.255.255.0

 

 

 

 

Gateway address

0.0.0.0

 

 

 

 

Port number

64758 (fixed)

 

 

 

 

Speed auto/10M

0 (fixed)

 

 

 

 

: Necessary : As necessary

: Not necessary

(2) CNC monitor

Item

Set value

Setting necessity at

GOT connection

 

 

IP address

192.168.0.19

 

 

 

 

Subnet mask

255.255.255.0

 

 

 

 

Gateway address

0.0.0.0

 

 

 

 

Port number

64758 (fixed)

 

 

 

 

Speed auto/10M

0 (fixed)

 

 

 

 

: Necessary : As necessary

: Not necessary

(3)Communication check

The CNC C70 can communicate with the GOT when INIT.LED of the CNC C70 is lit.

For confirming the communication state, refer to the following.

Checking communication state of CNC C70

[Controller Setting] and [Ethernet] of GT Designer3

(1) Controller setting

Item

Set value (Use default value)

GOT NET No.

1

 

 

GOT PLC No.

1

 

 

GOT IP Address

192.168.0.18

 

 

GOT Port No.

5001

(Communication)

 

 

 

GOT Port No.

5012

(Ethernet Download)

 

 

 

Default Gateway

0.0.0.0

 

 

Subnet Mask

255.255.255.0

 

 

Retry

3times

 

 

Startup Time

3sec

 

 

Timeout Time

3sec

 

 

Delay Time

0ms

 

 

8 - 42

8. ETHERNET CONNECTION

 

8.4 PLC Side Setting