This section describes the settings of the GOT and Display I/F (CNC C70) in the following case of the system configuration.
POINT
Display I/F (CNC C70)
For details of the Display I/F (CNC C70), refer to the following manual.
C70 Series SET UP MANUAL
System configuration
■ [Controller Setting] and [Ethernet] of GT
<GOT> (The settings other than the following are set to the default)
Network No. | : 1 |
PLC No. | : 1 |
IP address | : 192.168.0.18 |
Port No. | : 5001 |
Communication format : UDP (fixed)
<Q17nNCCPU> (The settings other than the following are set to the default)
Network No. | : 239 |
PLC No. | : 2 |
IP address | : 192.168.0.19 |
Port No. | : 5001 |
Communication format | : UDP(fixed) |
■ IP address settings of CNC C70
IP address settings of CNC C70
(1) Remote monitor tool
Item | Set value | Setting necessity at | |
GOT connection | |||
|
| ||
IP address | 192.168.0.19 |
| |
|
|
| |
Subnet mask | 255.255.255.0 |
| |
|
|
| |
Gateway address | 0.0.0.0 |
| |
|
|
| |
Port number | 64758 (fixed) |
| |
|
|
| |
Speed auto/10M | 0 (fixed) |
| |
|
|
|
: Necessary : As necessary | : Not necessary |
(2) CNC monitor
Item | Set value | Setting necessity at | |
GOT connection | |||
|
| ||
IP address | 192.168.0.19 |
| |
|
|
| |
Subnet mask | 255.255.255.0 |
| |
|
|
| |
Gateway address | 0.0.0.0 |
| |
|
|
| |
Port number | 64758 (fixed) |
| |
|
|
| |
Speed auto/10M | 0 (fixed) |
| |
|
|
|
: Necessary : As necessary | : Not necessary |
(3)Communication check
The CNC C70 can communicate with the GOT when INIT.LED of the CNC C70 is lit.
For confirming the communication state, refer to the following.
■Checking communication state of CNC C70
[Controller Setting] and [Ethernet] of GT Designer3
(1) Controller setting
Item | Set value (Use default value) | |
GOT NET No. | 1 | |
|
| |
GOT PLC No. | 1 | |
|
| |
GOT IP Address | 192.168.0.18 | |
|
| |
GOT Port No. | 5001 | |
(Communication) | ||
| ||
|
| |
GOT Port No. | 5012 | |
(Ethernet Download) | ||
| ||
|
| |
Default Gateway | 0.0.0.0 | |
|
| |
Subnet Mask | 255.255.255.0 | |
|
| |
Retry | 3times | |
|
| |
Startup Time | 3sec | |
|
| |
Timeout Time | 3sec | |
|
| |
Delay Time | 0ms | |
|
|
8 - 42 | 8. ETHERNET CONNECTION |
| 8.4 PLC Side Setting |